VLT
®
8000 AQUA
■
LC filter VLT 8042-8062 200-240 V /
8072-8602 380 - 480 V
The table and the drawing give the measurements of IP
20 LC filters. IP 20 LC filters must be integrated and
protected against dust, water and aggressive gases.
Max. motor cable length:
- 150 m screened/armoured cable
- 300 m unscreened/unarmoured cable
If EMC standards are to be complied with:
- EN 55011-1B: Max. 50 m screened/armoured
cable
- EN 55011-1A: Max. 150 m screened/armoured
cable
LC-filter IP 20
LC type
A [mm]
B [mm]
C [mm]
D [mm]
E [mm]
F [mm]
G [mm]
Weight [kg]
175Z4701
740
550
600
70
175Z4702
740
550
600
70
175Z4703
740
550
600
110
175Z4704
740
550
600
120
175Z4705
830
630
650
220
175Z4706
830
630
650
250
175Z4707
830
630
650
250
175Z3139
1350
800
1000
350
175Z3140
1350
800
1000
400
175Z3141
1350
800
1000
400
175Z3142
1350
800
1000
470
MG.83.A2.02 - VLT is a registered Danfoss trademark
22