VLT
®
8000 AQUA
All about VLT 8000
AQUA
■
Peak voltage on motor
When a transistor in the inverter is opened,
the voltage across the motor increases by a
dU/dt ratio that depends on:
-
the motor cable (type, cross-section, length
screened or unscreened)
-
inductance
The natural induction causes an overshot U
PEAK
in the
motor voltage before it stabilises itself at a level which
depends on the voltage in the intermediate circuit. The
rise time and the peak voltage U
PEAK
affect the service
life of the motor. If the peak voltage is too high, motors
without phase coil insulation are the ones that will
primarily be affected. If the motor cable is short (a few
metres), the rise time and peak voltage are lower.
If the motor cable is long (100 m), the rise time
and peak voltage will increase.
If very small motors are used without phase coil
insulation, it is recommended to fit a LC filter
after the frequency converter.
Typical values for the rise time and peak voltage
U
PEAK
are measured on the motor terminals
between two phases.
To obtain approximate values for cable lengths
and voltages not mentioned below, use the
following rules of thumb:
1. Rise time increases/decreases proportionally with
cable length.
2. U
PEAK
= DC link voltage x 1.9
(DC link voltage = Mains voltage x 1.35).
3.
Data are measured according to IEC 60034-17.
Cable lengths are in metres/feet.
VLT 8006-8011 / 380-480 V
Cable
length
Mains
volt-
age
Rise time
Peak
voltage
dU/dt
50m/164ft
500 V
0.5
µ
sec.
1230 V
1968 V/
µ
sec.
150m/492ft
500 V
1
µ
sec.
1270 V
1270 V/
µ
sec.
50m/164ft
380 V
0.6
µ
sec.
1000 V
1333 V/
µ
sec.
150m/492ft
380 V
1.33
µ
sec.
1000 V
602 V/
µ
sec.
VLT 8016-8122 / 380-480 V
Cable
length
Mains
volt-
age
Rise time
Peak
voltage
dU/dt
32m/105ft
380 V
0.27
µ
sec.
950 V
2794 V/
µ
sec.
70m/230ft
380 V
0.60
µ
sec.
950 V
1267 V/
µ
sec.
132m/433ft
380 V
1.11
µ
sec.
950 V
685 V/
µ
sec.
VLT 8152-8352 / 380-480 V
Cable
length
Mains
volt-
age
Rise time
Peak
voltage
dU/dt
70m/230ft
400 V
0.34
µ
sec.
1040 V
2447 V/
µ
sec.
VLT 8452-8652 / 380-480 V
Cable
length
Mains
volt-
age
Rise time
Peak
voltage
dU/dt
29m/95ft
500 V
0.71
µ
sec.
1165 V
1389 V/
µ
sec.
29m/95ft
400 V
0.61
µ
sec.
942 V
1233 V/
µ
sec.
VLT 8002-8011 / 525-600 V
Cable
length
Mains
volt-
age
Rise time
Peak
voltage
dU/dt
35m/115ft
600 V
0.36
µ
sec.
1360 V
3022 V/
µ
sec.
VLT 8016-8072 / 525-600 V
Cable
length
Mains
volt-
age
Rise time
Peak
voltage
dU/dt
35m/115ft
575 V
0.38
µ
sec.
1430 V
3011 V/
µ
sec.
VLT 8052-8402 / 525-690 V
Cable
length
Mains
voltage
Rise time
Peak
voltage
dU/dt
25m/82ft
690 V
0.59
µ
sec.
1425
1983 V/
µ
sec.
25m/82ft
575 V
0.66
µ
sec.
1159
1428 V/
µ
sec.
25m/82ft
690 V
1)
1.72
µ
sec.
1329
640 V/
µ
sec.
VLT 8502-8652 / 525-690 V
Cable
length
Mains
voltage
Rise time
Peak
voltage
dU/dt
25m/82ft
690 V
0.57
µ
sec.
1540
2230 V/
µ
sec.
25m/82ft
575 V
0.25
µ
sec.
2510 V/
µ
sec.
25m/82ft
690 V
1)
1.13
µ
sec.
1629
1149 V/
µ
sec.
1) With Danfoss dU/dt filter.
MG.83.A2.02 - VLT is a registered Danfoss trademark