VLT
®
8000 AQUA
■
Use on isolated mains
See section
RFI Switch
regarding use on isolated mains.
It is important to follow the recommendations regarding
installation on IT-mains, since sufficient protection
of the complete installation must be observed.
Not taking care using relevant monitoring devices
for IT-mains may result in damage.
It is the responsibility of the user or the
person installing the VLT to provide proper
earthing/grounding, as well as motor
overload and branch circuit protection according to
local codes such as the Nation Electrical Code (NEC).
NB!:
Electrostatic Precaution; Electrostatic discharge
(ESD). Many electronic components are
sensitive to static electricity. Voltages so low
that they cannot be felt, seen or heard, can reduce
the life, affect performance, or completely destroy
sensitive electronic components. When performing
service, proper ESD equipment should be used to
prevent possible damage from occurring.
The frequency converter contains dangerous
voltages when connected to mains voltage.
After disconnecting from mains wait at least
15 minutes for VLT 8006-8062, 200-240 V
15 minutes for VLT 8006-8072, 380-480 V
20 minutes for VLT 8102-8352, 380-480 V
40 minutes for VLT 8452-8652, 380-480 V
4 minutes for VLT 8002-8006, 525-600 V
15 minutes for VLT 8008-8027, 525-600 V
30 minutes for VLT 8032-8072, 525-600 V
20 minutes for VLT 8052-8402, 525-690 V
30 minutes for VLT 8502-8652, 525-690 V
before touching any electrical components. Also
make sure that other voltage inputs have been
disconnected, such as external 24 VDC and
load-sharing (linkage of DC intermediate circuit). Only
a competent electrician should carry out the electrical
installation. Improper installation of the motor or the
VLT may cause equipment failure, serious injury or
death. Follow this manual and National Electrical
Codes (NEC) and local safety codes.