Synchronizing controller
68
MG.10.N4.02 - VLT is a registered Danfoss trademark
Parameter 744 Step width: In marker synchronization mode, Offset Parameter 740 is changed
by this value when Terminal 32 or Terminal 33 is activated.
Parameter 745 Slave speed factor: Record the factor by which the slave speed must be
multiplied, so that the desired value is displayed. To calculate the value use
the following formula:
Factor =
value
Display
resolution
er
Slaveencod
N
Set
_
*
60
_
*
400
*
Example:
resolution 1024 increments, desired display 100 at 1500
1
/
min
Factor =
1500
400 1024
60 100
1
min
.
.
*
*
*
Inkr
Umdr
=
102400
Parameter 746 Master speed factor: Record the factor by which the master speed must be
multiplied, so that the desired value is displayed. To calculate the value use
the following formula:
Factor =
value
Display
resolution
der
Masterenco
N
Set
_
*
60
_
*
400
*
Parameter 747 Synchronizing error display factor: Record the factor by which the error must
be multiplied, so that the desired value is displayed. To calculate the value,
use the following formula:
Factor =
value
Display
resolution
er
Slaveencod
N
Set
_
*
60
_
*
400
*
Store your data settings by means of Store Input (I4) or by changing Parameter 710 to “1”.