Synchronizing controller
48
MG.10.N4.02 - VLT is a registered Danfoss trademark
Parameter 746
Master speed factor: Record the factor by which the master speed must be
multiplied, so that it can be displayed. Use the following formula:
Factor =
value
Display
resolution
der
Masterenco
N
Set
_
*
60
_
*
400
*
Parameter 747
Synchronizing error display factor: This factor must be 100, the synchronizing
error is then displayed in RPM related to the slave.
Store your data settings by means of Store Input (I4) or by changing Parameter 710 to “1”.
Operation and operating functions
After all the values have been set as described and the controller optimized for the application,
normal operation can begin.
Starting synchronization
Synchronization with the master is achieved by closing the SyncStart contact (I1); the drive
accelerates the maximum permitted acceleration to the speed of the master (calculated by
means of the gear ratio).
Stopping synchronization
When the SyncStart contact (I1) is opened, the slave is stopped at the permitted acceleration.
Fine setting of the gear ratio
Fine setting of the gear ratio can now be undertaken by means of Inputs 32 + 33. This setting is
only temporary, i.e. the fine setting data will be lost as soon as VLT 5000 is disconnected from
the mains. If the setting is to be saved, a Store operation must be carried out by closing the
Store contact (I4) or by means of Parameters 710 before the VLT 5000 is switched off.
Switching to another gear ratio
During synchronization, a new gear ratio can be selected at Inputs 16 and 17. The gear ratio is
then activated by means of the Switching Input (I2). The slave will then proceed at the permitted
acceleration to this new gear ratio.
Error procedure
Errors of tracking, over current etc. make the drive stop and the Ready output (O8) is reset.
Reset is done with Input 27 or fieldbus bit 1.9.
Reset is also possible with the [STOP/RESET] key of the local control panel of the drive. This is
only possible if the local stop function is disabled in parameter 014.
Note: You cannot stop the drive via the local control panel if local stop is disabled.
In case the drive has stopped because of earth fault or short-circuit, do disconnect the drive
from the mains before you reset!