Synchronizing controller
36
MG.10.N4.02 - VLT is a registered Danfoss trademark
797
Test run; Program 1:
“Track error“: The track error is displayed in quad counts.
Synchronous operation; Program 2:
“Sync-error”: The synchronization error is displayed with the value calculated in Parameter
747.
798
“Slave speed”: The slave speed is displayed with the value calculated in Parameter 745.
799
“Master speed”: The master speed is displayed with the value calculated in Parameter
746.
Initializing the parameters
It is possible to restore parameter default values by means of the initialise function in parameter 620.
All parameter except parameter 500, 501, 600-605, 615-617 will be reset to factory default setting.
NOTE: The VLT must be in stop mode before initialising can be carried out.
Procedure for initialising:
1. Select initialise in parameter 620
2. Press the [OK] key
3. Set parameter 710 to “1”. Wait until it changes to “0”(app. 0.5 sec)
4. Switch off mains supply and wait until the display is dark
5. Switch on the mains supply