Synchronizing controller
30
MG.10.N4.02 - VLT is a registered Danfoss trademark
745
Synchronous operation; Program 2:
Slave speed factor: Enter here the factor by which the slave speed must be scaled, so
that the desired value is displayed. The following formula applies for calculation of the
factor:
Factor =
value
Display
resolution
er
Slaveencod
N
Set
_
*
60
_
*
400
*
Example: Resolution 1024 PPR, desired display 100 at 1500
1
/
min
Factor =
=
100
*
60
1024
*
400
*
1500
.
Re
.
min
1
v
Incr
102400
746
Synchronous operation; Program 2:
Master speed factor: Enter here the factor by which the master speed must be scaled, so
that desired value is displayed. The formula for calculation of the factor is:
Factor =
value
Display
resolution
der
Masterenco
N
Set
_
*
60
_
*
400
*
747
Synchronous operation; Program 2:
Synchronizing error display factor: Enter the factor by which the error must be scaled,
so that the desired value is displayed. The formula for calculation of the factor is:
Speed synchronization: The factor should be 100, the synchronizing error is then
displayed in RPM related to the slave.
Position synchronization:
Factor =
Userunit
resolution
er
Slaveencod
_
*
400
*
Example: Resolution 1024 PPR, user unit is 100 mm/revolution
Factor
=
4096
100
1024
*
400
*
=
748
Virtual master reference value: Select here the type of reference value for the virtual
master.
0
= reference value signal 0..
±
10V via Terminal 53,
1
= reference value signal 0..
±
20mA via Terminal 60,
2
= reference value can be set via Parameter 216.
3
= reference value is set via Field bus (PCD 2). +/- 1000 corresponds to maximum
virtual master velocity (parameter 750).