6 fixed speeds, max. speed 60 Hz
1 speed = 6 Hz (10%), 2 speeds = 12 Hz (20%),
3 speeds = 18 Hz (30%), 4 speeds = 24 Hz (40%),
5 speeds = 42 Hz (70%), 6 speeds = 60 Hz (100%)
Connection examples
Example 6:
NB:
Screen for control cables must be
connected as described in the chapter on
EMC-correct installation.
All settings are based on factory settings, but
motor data (parameters 103-105) must be set
according to the motor connected
The following must be programmed:
Function
Parameter no.
Parameter value
Setup selection
001
multi setup
Setup selection
400
setup selection
Speed selection
406
digital ref. selection
Select setup 1
Max. frequency
202
60 Hz
Digital reference 1
205
10%
Digital reference 2
206
20%
Digital reference 3
207
30%
Digital reference 4
208
40%
Select setup 2
Max. frequency
202
60 Hz
Digital reference 5
205
70%
Digital reference 6
205
100%