32
MG.30.A7.02 - VLT
®
is a registered Danfoss trademark
Terminal 16 / par. 400
✭
✭
✭
✭
✭
Reset
Stop *)
Freeze reference
Thermistor **)
Setup select
Terminal 17 / par. 401
Reset
Stop *)
✭
✭
✭
✭
✭
Freeze ref.
Pulse 100 Hz
Pulse 1kHz
Pulse 10 kHz
Terminal 18 / par. 402
✭
✭
✭
✭
✭
Start
Pulse start
No function
Terminal 19 / par. 403
✭
✭
✭
✭
✭
Reversing
Start revers
★★★
)
No function
Terminal 27 / par. 404
Quick stop *)
DC-brake *)
Stop *)
Terminal 29 / par. 405
✭
✭
✭
✭
✭
Jogging
Freeze jogging
Freeze reference
Digital reference
Ramp selection
Terminal 32 / par. 406
Speed up
Speed select
Setup select
✭
✭
✭
✭
✭
4
Setup extended
Terminal 33 / par. 406
Speed down
Description of terminals
✭
✭
✭
✭
✭
Motor
coasting *)
Reset and
motor coasting *)
Cross reference for terminals/parameter functions.
✭
✭
✭
✭
✭
= Factory setting.
*) Must be with break contact function (NCL), since the function is activated at 0 V on the input.
**) Choose the thermistor function if terminal 50 (10 V
D.C.
) and terminal 16 (parameter 400) are connected.
***) Terminal 19 is pulse start revers if terminal 18 is set to pulse start
Connection examples
The following shows 8 different connection examples with relevant programming suggestions
Example 1:
Connection examples
START/STOP REVERSING Reference: 4-20 mA ~ 0-100% speed
NB:
Screen for control cables must be
connected as described in the chapter on
EMC-correct installation.
All settings are based on factory settings, but
motor data (parameters 103-105) must be set
according to the motor connected.