27
MG.30.A7.02 - VLT
®
is a registered Danfoss trademark
Mains supply 3 x 440/460/500 V
Technical data
According to international VDE and UL/CSA requirements
VLT type
3060
3075
3100
3125
3150
3200
3250
Constant torque (CT):
Output current
I
VLT,N
[A]
77
96
124
156
180
240
302
I
VLT,MAX
[A](60s)
116
144
186
234
270
360
453
Output
S
VLT,N
[kVA]
67
83
107
135
156
208
262
S
VLT,MAX
(60s) [kVA]
100
125
161
203
234
312
392
Typical shaft output
P
VLT,N
[kW]
55
75
90
110
132
160
200
Quadratic torque (VT):
Output current
I
VLT,N
[A]
96
124
156
180
240
302
361
I
VLT,MAX
[A](60s)
106
136
172
198
264
332
397
Output
S
VLT,N
[kVA]
83
107
135
156
208
262
313
Typical shaft output
P
VLT,N
[kW]
75
90
110
132
160
200
250
Max. cable cross-section
[mm
2
]
70
70
150
150
150
2 x 95
2 x 95
Max. motor cable length
[m]
300
Output voltage
U
M
[%]
0-100 of mains voltage
Output frequency
f
M
[Hz]
0-120 or 0-500; programmable
Rated motor voltage
U
M,N
[V]
380/400/415/440/460/500
Rated motor frequency
f
M,N
[Hz]
50/60/87/100
Thermal protection during operation
Integrated thermal motor protection (electronic); thermistor
to DIN 44081
Switching on output
Unlimited (frequent switching on output may result in fault message)
Ramp times
[s]
0.1 - 3600
VLT type
3060
3075
3100
3125
3150
3200
3250
Input current
I
L,N
[A]
75.8
94.4
123.4
155.3
177.1
238.9
307.6
I
L,MAX
(60s)[A]
113.7
141.6
185.1
233.0
265.7
358.4
461.4
Quadratic load
I
L,N
[A]
94.4
123.4
155.3
177.1
238.9
307.6
359.3
I
L,MAX
(60s)[A]
106.0
136.0
172.0
198.0
264.0
332.0
397.0
Max. cable cross-section
[mm2]
120.0
120.0
2 x 120 2 x 120 2 x 120
2 x 240
2 x 240
Max. pre-fuses
1)
[A]
150.0
150.0
250.0
250.0
300.0
450.0
500.0
Supply voltage (VDE 0160)
[V]
3 x 380/400/415/440/460/500 ±10%
Supply frequency
[Hz]
50/60
Power factor / cos.
ϕ
1
0.9/1.0
Efficiency
0.96 at 100% load
Switching on input
times/min.
1
VLT type
3060
3075
3100
3125
3150
3200
3250
Weight (kg)
IP 21
147
147
211
211
220
306
306
IP 54
147
147
211
211
220
306
306
Power loss at max. load CT [W]
Front
423
529
713
910
1091
1503
1812
Heat sink
859
1074
1447
1847
2216
3051
3679
Power loss at max. load VT [W]
Front
529
713
910
1091
1503
1812
2209
Heat sink
1074
1447
1847
2216
3051
3679
4485
Enclosure
IP 21 / IP 54, NEMA 1/12
Vibration test
[g]
0.7
Relative humidity
[%]
VDE 0160 5.2.1.2.
Ambient temperature
[°C]
-10
→
+40 at full load
2)
(VT) -10
→
+45 (CT)
2)
(to VDE 0160)
[°C]
-30/25
→
+65/70 in storage/transport
Frequency converter protection
Jord- og kortslutningssikker
EMC standards
Emission
EN 55011, EN 55014
(See section “EMC test results”)
Immunitet
EN 50082-2, IEC 1000-4-2, IEC 1000-4-3, IEC 1000-4-4,
IEC 1000-4-5 VDE 0160
1) Bussman rapid type JJS integrated.
2) In the range -10 to 0°C, the equipment can start and run; however, the display values and certain operating characteristics will not fulfil the
specifications.