112
MG.30.A7.02 - VLT
®
is a registered Danfoss trademark
Parameter description
4.. Inputs and outputs
✮
= Factory setting. Text in ( ) = Display text.
The figures in [ ] are used in bus communication.
414
Time out
(Time out)
Value:
0 - 99 OFF
✭
100 OFF
If one of the “live zero” signals has been
selected (e.g. 4-20 mA) and this is less
than 2 mA, a fault message and a required
operating status after expiry of the pro-
grammed interval are activated.
The required operating status is selected in
parameter 415.
The VLT
®
’s reference can be frozen to the
current value, go to stop, go to the jogging
frequency entered in parameter 203, or go
to the maximum frequency in parameter
202.
The function is not active for local speed
reference (para. 004) when open loop or
slip compensation is selected (para 101).
415
Time out function
(Time out act.)
Value:
✭
Freeze (freeze)
[0]
Stop (stop)
[1]
Jogging (jog)
[2]
Max. speed (max)
[3]