110
MG.30.A7.02 - VLT
®
is a registered Danfoss trademark
You can use relay outputs 01 and 04 to
indicate status and warnings.
The relay is activated when the conditions
for the selected data values are fulfilled.
Activation/deactivation can be delayed in
parameters 316 and 317.
When relay output 01 is not
active there
is connection between terminals 01 and
terminal 03, but no connection between
terminal 01/03 and terminal 02.
(Changeover contact).
Description of choices:
[0] [12]: See explanation in parameter 407
[17]. Motor magnetized must be selected
for use of the relay for brake control with
external brake. (See description of brake
control on p. 69).
Value:
Control ready (control ready)
[0]
Unit ready (unit ready)
[1]
Unit ready remote control
(UNT RDY RCTL)
[2]
Enabled (enabled no WR)
[3]
Running (running)
[4]
Running no warning (RUNNING NOWR) [5]
Running in range
(RUNinRANGE)
[6]
Speed = reference no warning
(RUN@REF no WR)
[7]
Alarm (alarm)
[8]
Alarm or warning (alarm/warn)
[9]
Current limit (current limit)
[10]
Out of frequency range
(OUT FRQ RGE)
[11]
Out of current range
(OUT CURR RGE)
[12]
Motor thermal overload
(mot. therm.W)
[13]
✭
Ready and no motor
thermal overload
(ready-mot.OK)
[14]
Ready and no motor (rdy.mot.rem) [15]
Ready and no over/undervoltage
(ready + D.C. V ok)
[16]
Motor magnetized (motor mag.)
[17]
409
Relay output 01
(Relay 01)
Value:
Control ready (control ready)
[0]
Unit ready (unit ready)
[1]
Unit ready remote control
(UNT RDY RCTL)
[2]
Enabled (enabled no WR)
[3]
Running (running)
[4]
Running no warning
(running no WR)
[5]
Running in range
(RUNinRANGE)
[6]
Speed = reference no warning
(RUN@REF no WR)
[7]
Alarm (alarm)
[8]
Alarm or warning (alarm/warn)
[9]
Current limit (current limit)
[10]
Out of frequency range
(OUT FRQ RGE)
[11]
Out of current range
(OUT CURR RGE)
[12]
0 - 100 Hz
0-20 mA
[13]
0 - 100 Hz
4-20 mA
[14]
✭
0 - f
MAX
0-20 mA
[15]
0 - f
MAX
4-20 mA
[16]
REF
MIN
- REF
MAX
0-20 mA
[17]
REF
MIN
- REF
MAX
4-20 mA
[18]
FB
MIN
- FB
MAX
0-20 mA
[19]
FB
MIN
- FB
MAX
4-20 mA
[20]
0 - I
MAX
0-20 mA
[21]
0 - I
MAX
4-20 mA
[22]
0 - I
LIM
0-20 mA
[23]
0 - I
LIM
4-20 mA
[24]
0 - T
MOTOR, RATED 100%
0-20 mA
[25]
0 - T
MOTOR, RATED 100%
4-20 mA
[26]
408
Signal output 45
(Output 45)
See breakdown of parameter 407.
✮
= Factory setting. Text in ( ) = Display text.
The figures in [ ] are used in bus communication.
Parameter description
4.. Inputs and outputs