Compressor Status
Description
Trigger Method
Troubleshooting
l
Review the fault log for actual suction pressure and temperature, entering air/water
temperature (if available) and other conditions that are recorded at the time of fault.
l
Verify suction pressure/temperature sensor. Refer to Section 4.32.3
Pressure/Temperature Sensor Verification on page 246.
Table 5-7 Compressor Status 2 Faults
Compressor Status 2
Description
Trigger
Method
Troubleshooting
Suction Pressure
Sensor Fault
RFT
l
Sensor errors occur when the sensor is providing a reading that is outside the normal readable
temperature range and therefore must have an error in the reading or functional problem with the
sensor
l
Verify the associated sensor and related connections
Discharge
Pressure Sensor
Fault
RFT
l
Sensor errors occur when the sensor is providing a reading that is outside the normal readable
temperature range and therefore must have an error in the reading or functional problem with the
sensor
l
Verify the associated sensor and related connections
Suction
Temperature
Sensor Fault
RFT
l
Sensor errors occur when the sensor is providing a reading that is outside the normal readable
temperature range and therefore must have an error in the reading or functional problem with the
sensor
l
Verify the associated sensor and related connections
Discharge
Temperature
Sensor Fault
RFT
l
Sensor errors occur when the sensor is providing a reading that is outside the normal readable
temperature range and therefore must have an error in the reading or functional problem with the
sensor
l
Verify the associated sensor and related connections
Inverter
Temperature
Sensor Fault
RFT
l
Sensor errors occur when the sensor is providing a reading that is outside the normal readable
temperature range and therefore must have an error in the reading or functional problem with the
sensor
l
Verify the associated sensor and related connections
Cavity
Temperature
Sensor Fault
RFT
l
Sensor errors occur when the sensor is providing a reading that is outside the normal readable
temperature range and therefore must have an error in the reading or functional problem with the
sensor.
l
Verify the associated sensor and related connections
Soft Start
Temperature
Sensor Fault
RFT
l
Sensor errors occur when the sensor is providing a reading that is outside the normal readable
temperature range and therefore must have an error in the reading or functional problem with the
sensor.
l
Verify the associated sensor and related connections
Invalid Bearing
Calibration Fault
INS
l
If a bearing calibration is not saved in the EEPROM, this fault will be triggered, a valid calibration is
required prior to the compressor accepting demand.
l
Calibrate the compressor bearings using the Calibration Tool and save to EEPROM. Cycle power and
verify the calibration is retained in EEPROM.
Inverter Cooling
Control Fault
AFT
l
Refer to Table 5-6 Compressor Status on page 255 regarding High Inverter Temperature Fault
Troubleshooting
Motor Cooling
Control Fault
AFT
l
Refer to Table 5-6 Compressor Status on page 255 regarding High Cavity Temperature Fault
Troubleshooting
M-SV-001-EN Rev. H-1/23/2023 Page 259 of 294
Summary of Contents for Turbocor TT Series
Page 2: ...THIS PAGE INTENTIONALLY LEFT BLANK Page 2 of 294 M SV 001 EN Rev H 1 23 2023...
Page 14: ...Page 14 of 294 M SV 001 EN Rev H 1 23 2023 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 16: ...Page 16 of 294 M SV 001 EN Rev H 1 23 2023 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 18: ...Figure 1 2 New Type Code Page 18 of 294 M SV 001 EN Rev H 1 23 2023...
Page 46: ...Page 46 of 294 M SV 001 EN Rev H 1 23 2023 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 250: ...Page 250 of 294 M SV 001 EN Rev H 1 23 2023 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 268: ...Figure 5 3 Bearing Calibration Flow Page 268 of 294 M SV 001 EN Rev H 1 23 2023...
Page 274: ...Page 274 of 294 M SV 001 EN Rev H 1 23 2023 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 286: ...Page 286 of 294 M SV 001 EN Rev H 1 23 2023 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 290: ...Page 290 of 294 M SV 001 EN Rev H 1 23 2023 THIS PAGE INTENTIONALLY LEFT BLANK...