Component
Test Point
Expected Value
Verification Section
Measured
Value
F4 & F5
30-38Ω
4.14.2.2 Verifying Soft Start
Fuses
Solenoid Actuators
4.8 W
108Ω – 132Ω
9.3 W
56.25Ω – 68.75Ω
Stator Resistance
Phase 1:2
>0.0Ω and <1Ω
4.23.4.2 Stator Resistance
Verification
Phase 1:3
>0.0Ω and <1Ω
4.23.4.2 Stator Resistance
Verification
Phase 2:3
>0.0Ω and <1Ω
4.23.4.2 Stator Resistance
Verification
Stator Thermistor
Resistance
+ to -
150-300Ω at 70°
F (21°C)
4.23.4.2 Stator Resistance
Verification
M-SV-001-EN Rev. H-1/23/2023 Page 289 of 294