Table 5-3 Compressor Status 2 Faults
Compressor Status 2 Fault
Description
Suction Pressure Sensor Fault
Sensor errors occur when the sensor is providing a reading that is outside the normal readable range
and indicates an error in the reading, or a functional problem with the sensor. - only available in 4.X
Suction Temperature Sensor
Fault
Discharge Pressure Sensor Fault
Discharge Temperature Sensor
Fault
Inverter Temperature Sensor
Fault
Cavity Temperature Sensor Fault
Soft Start Temperature Sensor
Fault
Invalid Bearing Calibration Fault
A valid bearing calibration is not stored in the EEPROM.
Inverter Cooling Control Fault
The measured Inverter Temperature has exceeded the Cooling Control Fault limit after the Fault Delay timer has
expired. If the temperature rises above the fault limit, the fault delay timer will begin, if the temperature falls
below the fault limit, the timer will be reset, the compressor will stop if the timer expires.
Motor Cooling Control Fault
The measured Cavity Temperature has exceeded the Cooling Control Fault limit after the Fault Delay timer has
expired. If the temperature rises above the fault limit, the fault delay timer will begin, if the temperature falls
below the fault limit, the timer will be reset, the compressor will stop if the timer expires.
Table 5-4 Motor Fault Types
Motor/System Status
Description
Motor Single Phase Overcurrent
Fault
Measured peak current value of any single phase to motor (from Inverter) exceeds the fault limit.
DC Bus Overvoltage Fault
The measured DC bus voltage has exceeded the Maximum DC Bus Voltage limit, while RPM is >0
Motor High Current Fault
The motor current has exceeded Maximum Motor Current limit.
Inverter Error
Inverter reports a generic error, or communication to BMCC is lost.
Bearing Fault Active
If a Bearing Status Fault type is present, then the Bearing Fault Active is triggered. This is not an actual fault, only
an indication that a fault has occurred in the Bearing Status section.
Rotor Starting Torque Fault
Motor Current maximum has been exceeded during compressor start-up.
Low Inverter Current Fault
Measured current to motor (from Inverter) has not reached the Minimum Power limit.
DC Bus Under/Over Voltage
Fault
At 0 RPM: The measured DC Bus voltage is measured lower or higher than the DC Bus Under or Over Voltage Fault
limits.
24VDC Under/Over Voltage
Fault
The measured 24VDC supply is outside the range of the low or high limit.
Low Motor Back EMF Fault
The calculated motor back EMF has fallen below the minimum Back EMF limit.
EEPROM Checksum Fault
An error (checksum error) occurs reading the data table from the EEPROM.
Generator Mode Active
At greater than 0 RPM and DC bus voltage low, Generator mode is enabled, switching the Inverter to rectifier
function to maintain the DC bus voltage until the shaft comes to a stop and delevitates.
SCR Ripple Voltage Fault
The DC bus voltage ripple exceeds the SCR Voltage Ripple Fault limit.
System in Startup mode
The compressor initialization has not finished. Please wait. Compressor is resetting after a power cycle. This is a
status message.
M-SV-001-EN Rev. H-1/23/2023 Page 253 of 294
Summary of Contents for Turbocor TT Series
Page 2: ...THIS PAGE INTENTIONALLY LEFT BLANK Page 2 of 294 M SV 001 EN Rev H 1 23 2023...
Page 14: ...Page 14 of 294 M SV 001 EN Rev H 1 23 2023 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 16: ...Page 16 of 294 M SV 001 EN Rev H 1 23 2023 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 18: ...Figure 1 2 New Type Code Page 18 of 294 M SV 001 EN Rev H 1 23 2023...
Page 46: ...Page 46 of 294 M SV 001 EN Rev H 1 23 2023 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 250: ...Page 250 of 294 M SV 001 EN Rev H 1 23 2023 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 268: ...Figure 5 3 Bearing Calibration Flow Page 268 of 294 M SV 001 EN Rev H 1 23 2023...
Page 274: ...Page 274 of 294 M SV 001 EN Rev H 1 23 2023 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 286: ...Page 286 of 294 M SV 001 EN Rev H 1 23 2023 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 290: ...Page 290 of 294 M SV 001 EN Rev H 1 23 2023 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 292: ...Page 292 of 294 M SV 001 EN Rev H 1 23 2023 THIS PAGE INTENTIONALLY LEFT BLANK...