Figure 5-1 Fault Trigger Methods
Fault Reset:
A fault that does not require a power cycle to clear (non-critical) can be reset in the following manner:
Interlock must be closed, set the Demand to "0" and afterwards to a value greater than 0. Now the fault is reset and
the compressor is ready to run. The assumption is that the cause of the fault has been rectified.
The Clear Faults button in the SMT Compressor Monitor can be used in software versions 4.0.0 and later. Also see the
OEM Programming Guide for additional fault reset options.
A fault demanding a power cycle (Lock-Out Fault) is resettable by cycling the mains power to the compressor. The
assumption is that the cause of the fault has been rectified. Refer to the following tables:
l
l
Table 5-8 Motor/System Status on page 260
l
Table 5-9 Bearing Status on page 263
Table 5-6 Compressor Status
Compressor Status
Description
Trigger Method
Troubleshooting
High Inverter
Temperature Fault
AFT
Consequence:
l
Indicates the Inverter cooling is insufficient. Repeated occurrences of this alarm can
result in Inverter failure.
l
If this fault occurs three (3) times within a 30-minute period, a Lock-Out Fault will occur.
l
The measured Inverter temperature must drop below the Maximum Drive Startup
Temperature before a restart can be attempted, otherwise the Compressor Monitor Tool
Control Status message “Above drive temperature limit waiting to cool down” will be
displayed.
Recommendation:
l
Ensure the liquid motor-cooling line has sufficient liquid supply and is not blocked.
l
Prevent prolonged operation at a pressure ratio less than 1.5.
o
Low Lift operation requires additional considerations, refer to the Applications
Manual
l
Verify the solenoids are operational and not blocked. Refer to Section 4.6.3 Solenoid
M-SV-001-EN Rev. H-1/23/2023 Page 255 of 294
Summary of Contents for Turbocor TT Series
Page 2: ...THIS PAGE INTENTIONALLY LEFT BLANK Page 2 of 294 M SV 001 EN Rev H 1 23 2023...
Page 14: ...Page 14 of 294 M SV 001 EN Rev H 1 23 2023 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 16: ...Page 16 of 294 M SV 001 EN Rev H 1 23 2023 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 18: ...Figure 1 2 New Type Code Page 18 of 294 M SV 001 EN Rev H 1 23 2023...
Page 46: ...Page 46 of 294 M SV 001 EN Rev H 1 23 2023 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 250: ...Page 250 of 294 M SV 001 EN Rev H 1 23 2023 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 268: ...Figure 5 3 Bearing Calibration Flow Page 268 of 294 M SV 001 EN Rev H 1 23 2023...
Page 274: ...Page 274 of 294 M SV 001 EN Rev H 1 23 2023 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 286: ...Page 286 of 294 M SV 001 EN Rev H 1 23 2023 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 290: ...Page 290 of 294 M SV 001 EN Rev H 1 23 2023 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 292: ...Page 292 of 294 M SV 001 EN Rev H 1 23 2023 THIS PAGE INTENTIONALLY LEFT BLANK...