performed, repetitive failure may occur. Note 
that an oil acidity test always proves helpful in-
diagnosis when undertaking compressor repla-
cement.

• Check that the replacement component has 
the same electrical and refrigeration perfor-
mance characteristics as the original one.

• Whenever piping needs to be modified, please 
refer to the 

«Safety measures prior to assem-

bly»

 section.

• For further details on replacement steps,refer 
to the previous sections of this manual.

Note:

 

In the event of compressor motor failure, 

flush and clean the entire circuit before replacing 
the compressor in order to remove acids and conta-
minants. Systematically install a new filter dryer 
on the liquid line. Prior to this step (if necessary), 
run the system for at least 2 hours with anti-acid 
cartridges (in such instances, the installation of a 
suction filter might also be required). After an ope-
rating period of approximately 2 weeks, check the 
level of oil acidity. If the oil acid test proves positive, 
drain and replace the oil, replace the anti-acid li-
quid line filter dryer cartridges and the suction filter 
previously installed. Repeat oil and filter dryer re-
placements until the system is clean and acid-free.
When there is no longer any sign of acidity, replace 

the anti-acid cartridges by the standard model and 
remove the suction strainer cartridge as required

.

 

14 - User advisory

Insist that all service operations only be per-
formed by qualified personnel.

 The condensing unit tubing and compressor 

surface temperatures may exceed 100°C (212°F) 
and cause severe bodily burns. Special precau-
tion must be taken when working around the 
compressor and refrigerant tubing. Moreover, a 
compressor in operation can generate very cold 
surface temperatures (as low as -45°C / -49°F), 
there by exposing personnel to the risk of free-
zing burns. 

 Pressure inside the compressor and refrige-

rant circuit can reach dangerously high levels 
(e.g. abnormal operation, fire,…) leading to 
personnel injury if suddenly released; therefore, 
never drill, weld or cut the compressor shell and 
adjacent tubing (release of liquid refrigerant can 
cause flash freezing on exposed skin). 

 Even though fans are fitted with safety guard 

it is recommended not to work on condenser 
while fans are running.

Be aware that the product warranty may be 
deemed null and void in the following cases:

• Modifications to the unit, unless approved by 
Danfoss Commercial Compressors, absence 
of nameplate, broken or dented components, 
shock marks, etc...
• Compressor opened by the customer or re-
turned unsealed (i.e. open discharge or suction 
ports), 

• Presence of rust or water inside the condensing 
unit circuit, 

• Addition of leak-detection fluid in the compres-
sor lubricant,

• Use of a refrigerant or lubricant not approved 
by Danfoss Commercial Compressors.,

• Any deviation from recommended instructions-
pertaining to installation, application or mainte-
nance,

• Use in mobile applications (boats, trains, truc-
ks,etc.) or under explosive atmospheric conditions.

The date of production of the condensing unit 
is indicated on the nameplate. Ensure that the 
model and serial number information is always 
transmitted with any claim filed regarding this 
product.

Summary of Contents for Optyma OP-MCRN030

Page 1: ...Instructions Condensing Units Optyma Integralrange Danfoss DCS CC 2018 08 FRCC PI 059 A1 ML 1 English English p 2 Deutsch German p 10 Fran ais French p 18 Polski Polish p 26...

Page 2: ...N108 OP LGQN136 NTZ096 NTZ108 NTZ136 693 5 1500 870 OP LGQN215 OP LGQN271 NTZ215 NTZ271 836 5 1500 870 35 0 10 20 30 40 50 30 25 20 15 10 5 0 5 10 15 Evaporating Temperature C R404A R507 Ambient Tempe...

Page 3: ...clearance 2 x unit length Fig 2 Fig 3 Fig 4 45 0 10 20 30 40 50 40 35 30 25 20 15 10 5 0 5 Evaporating Temperature C R404A R507 Ambient Temperature C 45 0 10 20 30 40 50 40 35 30 25 20 15 10 5 0 5 Eva...

Page 4: ...Instructions 4 Danfoss DCS CC 2018 08 FRCC PI 059 A1 02 SINGLE PHASE MODELS THREE PHASE MODELS...

Page 5: ...Instructions Danfoss DCS CC 2018 08 5 FRCC PI 059 A1 02 For R404A models Factory setting HP bar MBP 28 8 LBP 28 3 LP bar...

Page 6: ...stored in an ambient temperature of below 35 C 31 F or above 50 C 122 F Ensure that the condensing unit and its packa ging are not exposed to rain and or a corrosive flammable atmosphere 3 Safety meas...

Page 7: ...if necessary Vacuum pump A two stage vacuum pump with gas ballast valve 0 04 mbar standing vacuum shall be used its capacity is to be consistent with system volume Never use the compressor as a vacuu...

Page 8: ...perations condenser cleanliness fan operations etc If above check out OK the problem may be due to either refrigerant over charging or the presence of a non condensable e g air moisture in the circuit...

Page 9: ...nit tubing and compressor surface temperatures may exceed 100 C 212 F and cause severe bodily burns Special precau tion must be taken when working around the compressor and refrigerant tubing Moreover...

Page 10: ...0 5 10 15 Evaporating Temperature C R404A R507 Ambient Temperature C Umgebungstemperatur C Verdampfungstemperatur C 35 0 10 20 30 40 50 30 25 20 15 10 5 0 5 10 15 Evaporating Temperature C R448A R449A...

Page 11: ...Temperature C R404A R507 Ambient Temperature C Umgebungstemperatur C Verdampfungstemperatur C 45 0 10 20 30 40 50 40 35 30 25 20 15 10 5 0 5 Evaporating Temperature C R452A Ambient Temperature C Umge...

Page 12: ...Instruktion 12 Danfoss DCS CC 2018 08 FRCC PI 059 A1 03 EINPHASIGE MODELLE DREI PHASEN MODELLE...

Page 13: ...n Hg KP 15 15A 17W 17B KP17W B 060 539366 060 539466 ND auto ND auto HD man HD auto Einschalten ND HD ND HD Differenz Feste Differenz Ausschalten Manueller Test Einschalten Anzugsmoment 2 5 Nm Nur Kup...

Page 14: ...Reklamation an gezeigt werden Die gleiche Empfehlung gilt f r die F lle in denen die Transportanweisungen nicht eingehalten wurden Bitte hinsichtlich der Lagerung die auf dem Verpackungskarton aufged...

Page 15: ...Hochdruckseite angeschlossen sein um alle Anlagenteile gut evakuieren zu k nnen Empfohlene Vorgehensweise 1 Nach Abschluss der Lecksuche 2 ist der Druck in der Anlage auf ein Vakuum von 500 mHg 0 67 m...

Page 16: ...st Verdichter baut keinen Druck auf Bitte kontrollieren ob etwaige in der Anlage befind lichen Bypassventile geschlossen sind Befinden sich s mtliche Magnetventile tats chlich in der gew nschten Stell...

Page 17: ...nd Filtertrockneraustausch sind solange zu wiederholen bis die Anlage sauber und s urefrei ist SindkeineAnzeichenvonS uremehrerkennbar sind die Burnout Eins tze in der Fl ssigkeitslei tung durch eine...

Page 18: ...15 Evaporating Temperature C R404A R507 Ambient Temperature C Temp rature ambiante C Temp rature d vaporation C 0 10 20 30 40 50 30 25 20 15 10 5 0 5 10 15 20 Evaporating Temperature C R134a Ambient T...

Page 19: ...0 15 10 5 0 5 Evaporating Temperature C R404A R507 Ambient Temperature C Temp rature ambiante C Temp rature d vaporation C 45 0 10 20 30 40 50 40 35 30 25 20 15 10 5 0 5 Evaporating Temperature C R452...

Page 20: ...Instructions 20 Danfoss DCS CC 2018 08 FRCC PI 059 A1 04 MOD LES UNE SEULE PHASE TROIS MODES DE PHASE...

Page 21: ...rentiel fixe Point de renclenchement Test manuel Point de declenchement Couple de serrage 20 Nm Fil de cuivre uniquement Point de renclenchement Reset manuel Reglage d usine Reset manuel Reset convert...

Page 22: ...sauxintemp ries et ou des substances corrosives ou inflammables 3 Mesures de s curit avant montage Toute op ration de montage et d entretien doit tre effectu e par un personnel qualifi confor m ment...

Page 23: ...vide Utilisez des raccords et flexibles de gros dia m tre et les connecter aux vannes d arr t plut t qu au raccord Schrader Cette mesure permet d viter des pertes de charge excessives Niveau d humidit...

Page 24: ...aude et le com presseur d clenchera sur la protection moteur Si cela se produit le r armement peut prendre deux trois heures Bruit de fonctionnement anormal v rifiez l absence de retour de liquide au...

Page 25: ...d huile et cartouches de filtre jusqu ce que le syst me soit propre et exempt de tout acide Quand il n y a plus aucune trace d acide remplacez les cartouches anti acides par le mod le standard et ret...

Page 26: ...Evaporating Temperature C R404A R507 Ambient Temperature C 35 0 10 20 30 40 50 30 25 20 15 10 5 0 5 10 15 Evaporating Temperature C R448A R449A Ambient Temperature C 35 0 10 20 30 40 50 30 25 20 15 1...

Page 27: ...nit length 45 0 10 20 30 40 50 40 35 30 25 20 15 10 5 0 5 Evaporating Temperature C R404A R507 Ambient Temperature C 45 0 10 20 30 40 50 40 35 30 25 20 15 10 5 0 5 Evaporating Temperature C R452A Ambi...

Page 28: ...Instrukcje 28 Danfoss DCS CC 2018 08 FRCC PI 059 A1 49 MODELE POJEDYNCZEJ FAZY MODELE TR JFAZOWE...

Page 29: ...17B 060 539366 060 539466 LP auto LP auto HP man HP auto Ci nienie za czania R nica Sta a r nica Ci nienie wy czania Sprawdzian manualny Ci nienie za czania Tightening torque 20 lb in Use copper wire...

Page 30: ...ni ej 35 C ani powy ej 50 C Nale y upewni si czy urz dzenie i jego opa kowanie nie jest nara one na bezpo rednie dzia anie deszczu czynnik w atwopalnych oraz czynnik w powoduj cych korozj 3 rodki bezp...

Page 31: ...wory odcinaj ce wchodz w sk ad instalacji agregat skraplaj cy musi by izolowany od uk adu Istotne jest r wnie pod czenie pompy pr niowej po obydwu stronach tj wysokie go i niskiego ci nienia aby odess...

Page 32: ...e y sprawdzi uzwojenia silnika przy pomocy omomie rza Uwaga W przypadku gdy wewn trzne zabez pieczenie silnika wy czy silnik spr arki mo e up yn kilka godzin zanim ponowny start spr arki b dzie mo liw...

Page 33: ...i gu cieczowym na zwyk y odwad niaj cy i w razie potrzeby usun wk ad z filtra na stronie ssawnej 14 Wskaz wki dla u ytkownika Wszystkie czynno ci serwisowe powinny by wykonywane tylko i wy cznie przez...

Page 34: ...its products without notice This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed All...

Reviews: