background image

Instructions

© Danfoss | DCS (CC) | 2018.08  | 7

FRCC.PI.059.A1.02

• Avoid flare-type connections and exercise great 
care while brazing (use only state-of-the-art 
practices); apply a nitrogen gas flow to prevent 
oxidation inside the tubing, especially when 
HFC refrigerants are being used. All brazing ma-
terial is to contain a minimum of 5% silver.
• When brazing, protect the valves and all other 
unit components from torch heat damage 
(painted surfaces, gaskets, connecting box).

• Note that it is not necessary to remove com-
pressor shut-off valves for connection to the 
system, hence no need to replace associated 
gaskets. 

• Be sure to connect the required safety and control 
devices onto compressor shut-off valves or fittings.

• In case of oil return through the Schrader fitting 
on the compressor shell, make sure the internal 
valve is removed.

5 - Leak detection

Never use oxygen or dry air in order to avoid the 
risk of fire or explosion.

• Perform a leak detection test on the complete 
system by means of: a dry nitrogen pressure test, 
a mixture of nitrogen and the refrigerant to be 
used in the system, a helium leak test and/or a 
deep vacuum test.

• The test should be long enough in duration to 
ensure the absence of any slow leaks in the sys-
tem.

• Use tools specifically designed for detecting leaks.

• The low side test pressure must not exceed 1.1 
x Ps pressure indicated on the compressor name-
plate.

• For high side test pressure, do not exceed the pres-
sure indicated on the condensing unit nameplate. 

• Whenever the condensing unit is equipped 
with suction and liquid shut-off valves, these 
valves are to remain in the closed position while 
performing the leak test (condensing unit leak 
test already performed in the factory).

• Should a leak be discovered, proceed with re-
pair steps and repeat the leak detection. 

• When a deep vacuum leak detection test is se-
lected, observe the following:
  1) The level to reach is 500 μm Hg.
  2) Wait 30 min.
  3) If pressure increases rapidly, the system is 
not airtight. Locate and repair leaks. Restart the 
vacuum procedure, followed by steps 1, 2, etc.
  4) If pressure increases slowly, the system 
contains moisture inside. Break the vacuum with 
nitrogen gas and restart the vacuum procedure, 
followed by steps 1, 2, etc.
  5) Connect the compressor to the system by 
opening the valves. 
  6) Repeat the vacuum procedure, followed by 
steps 1, 2, etc.
  7) Break the vacuum with nitrogen gas. 
  8) Repeat the vacuum procedure, steps 1, 2; 
a vacuum of 500 μm Hg (0.67 mbar) should be 
reached and maintained for 4 hours. This pres-

sure is to be measured in the refrigeration sys-
tem, and not at the vacuum pump gauge.

 Do not use a megohmeter or apply power to the 

compressor while it is under vacuum, as this may 
cause motor winding damage (motor burn-out).

 Do not use colored leak detection fluids. Do 

not use chlorofluorocarbon in leak testing sys-
tems designed for HFC fluids.

6 - Vacuum dehydration procedure

Whenever possible (if shut-off valves are pre-
sent), the condensing unit must be isolated from 
the circuit. It is essential to connect the vacuum 
pump to both the LP & HP sides, in order to avoid 
dead-ending system parts.

Recommended procedure:
  1) Once leak detection has been completed,
  2) Pull down the system under a vacuum of 
500 μm Hg (0.67 mbar).
  3) When the vacuum level of 500 μm Hg has 
been reached, the system must be isolated from 
the pump.
  4) A vacuum of 500 μm Hg (0.67 mbar) has 
to be reached and maintained for 4 hours. This 
pressure is to be measured in the refrigeration 
system, and not at the vacuum pump gauge.

If pressure increases, restart the leak-detection 
procedure (refer to the «Leak detection» section 
of this manual if necessary).

Vacuum pump:
A two-stage vacuum pump with gas ballast 
valve (0,04-mbar standing vacuum) shall be 
used; its capacity is to be consistent with system 
volume. 
Never use the compressor as a vacuum pump. It 
is recommended to use large-diameter connec-
tion lines and to connect these lines to the shut-
off valves, rather than to the Schrader connec-
tion.
This recommendation allows avoiding excessive 
pressure losses.

Moisture level:
At the time of commissioning, system moisture 
content may be as high as 100 ppm. During ope-
ration, the liquid line filter dryer must reduce this 
level to < 20 ppm.

Additional notes:
• To improve moisture removal, the temperature 
of the system should not be lower than 10°C.

• A proper vacuum procedure is even more im-
portant with HFC and polyolester lubricant than 
it has “traditionally” been with HCFC (R22) or CFC 
and mineral oil.

• For further details, please refer to TI 3-026.

 Do not use a megohmeter or apply power to 

the compressor while it is under vacuum, as this 
may cause motor winding damage (motor burn-
out).

7 - Electrical connections

• Make sure the main power supply to the sys-
tem has been switched off and isolated, in ac-
cordance with applicable regulations, before 
performing any electrical connection.

• Please refer to Figs 5 and 6 for typical wiring 
connections and examine the specific wiring 
diagram located in the electrical box cover.
For further details, refer to the condensing unit 
guidelines.

• Note that Maneurop® compressors fitted on 
condensing units are protected against overhea-
ting and overloading by an internal safety motor 
protector. However, an external manual reset 
overload is recommended for protecting the cir-
cuit against over-current.

• The “must trip” value of this overload relay must 
be set in accordance with power line sizing and 
design and shall never exceed the “A max.” value 
stamped on the nameplate.

• On units equipped with an electrical box, all 
electrical connections (condenser fan motor, 
compressor motor, pressure control switch, 
crankcase heater, etc.) have already been wired at 
the factory. For single-phase compressors, start-
and-run capacitors are included in the connec-
ting box.

• The connecting box is equipped with screw type 
terminal blocks, for both power and control lines as 
well as earth terminals for grounding connections.

• All electrical components must be selected as 
per local standards and condensing unit compo-
nent requirements.

8 - Filling the system

• Before charging the refrigerant, verify that the 
oil level is between 1/4 and 3/4 on the com-
pressor oil sight glass and/or ensure that the oil 
charge of the original compressor is sufficient as 
regards system dimension and piping design:
  - An additional quantity of oil might be neces-
sary for line lengths (back and forth) in excess of 
20 m.
  - In the event additional oil is required, use 
only an approved lubricant (refer to the «Intro-
duction» section of this manual).

• Make sure the refrigerant used to fill the system 
is compatible with compressor design. Refer to 
the 

«Introduction»

 section of this manual for an 

approved list of refrigerants.

• Compressor switched off: the liquid refrigerant 
is charged into the condenser and/or liquid re-
ceiver in the liquid phase (compulsory for refri-
gerant blends).The charge must be asclose to 
the nominal system charge as possible in order 
to avoid both low pressure operations and ex-
cessive superheating at start-up. Throughout 
this operation, both compressor service valves 
must remain closed.

• To the extent possible, maintain the refrigerant 
charge below 2.5 kg per cylinder. Above this li-
mit, install a system, such as a pump-down cycle 
or suction line accumulator, to prevent against 
liquid flood-back into the compressor.

• Be sure that the refrigerant charge is suitable 
for both winter and summer operations.

Summary of Contents for Optyma OP-MCRN030

Page 1: ...Instructions Condensing Units Optyma Integralrange Danfoss DCS CC 2018 08 FRCC PI 059 A1 ML 1 English English p 2 Deutsch German p 10 Fran ais French p 18 Polski Polish p 26...

Page 2: ...N108 OP LGQN136 NTZ096 NTZ108 NTZ136 693 5 1500 870 OP LGQN215 OP LGQN271 NTZ215 NTZ271 836 5 1500 870 35 0 10 20 30 40 50 30 25 20 15 10 5 0 5 10 15 Evaporating Temperature C R404A R507 Ambient Tempe...

Page 3: ...clearance 2 x unit length Fig 2 Fig 3 Fig 4 45 0 10 20 30 40 50 40 35 30 25 20 15 10 5 0 5 Evaporating Temperature C R404A R507 Ambient Temperature C 45 0 10 20 30 40 50 40 35 30 25 20 15 10 5 0 5 Eva...

Page 4: ...Instructions 4 Danfoss DCS CC 2018 08 FRCC PI 059 A1 02 SINGLE PHASE MODELS THREE PHASE MODELS...

Page 5: ...Instructions Danfoss DCS CC 2018 08 5 FRCC PI 059 A1 02 For R404A models Factory setting HP bar MBP 28 8 LBP 28 3 LP bar...

Page 6: ...stored in an ambient temperature of below 35 C 31 F or above 50 C 122 F Ensure that the condensing unit and its packa ging are not exposed to rain and or a corrosive flammable atmosphere 3 Safety meas...

Page 7: ...if necessary Vacuum pump A two stage vacuum pump with gas ballast valve 0 04 mbar standing vacuum shall be used its capacity is to be consistent with system volume Never use the compressor as a vacuu...

Page 8: ...perations condenser cleanliness fan operations etc If above check out OK the problem may be due to either refrigerant over charging or the presence of a non condensable e g air moisture in the circuit...

Page 9: ...nit tubing and compressor surface temperatures may exceed 100 C 212 F and cause severe bodily burns Special precau tion must be taken when working around the compressor and refrigerant tubing Moreover...

Page 10: ...0 5 10 15 Evaporating Temperature C R404A R507 Ambient Temperature C Umgebungstemperatur C Verdampfungstemperatur C 35 0 10 20 30 40 50 30 25 20 15 10 5 0 5 10 15 Evaporating Temperature C R448A R449A...

Page 11: ...Temperature C R404A R507 Ambient Temperature C Umgebungstemperatur C Verdampfungstemperatur C 45 0 10 20 30 40 50 40 35 30 25 20 15 10 5 0 5 Evaporating Temperature C R452A Ambient Temperature C Umge...

Page 12: ...Instruktion 12 Danfoss DCS CC 2018 08 FRCC PI 059 A1 03 EINPHASIGE MODELLE DREI PHASEN MODELLE...

Page 13: ...n Hg KP 15 15A 17W 17B KP17W B 060 539366 060 539466 ND auto ND auto HD man HD auto Einschalten ND HD ND HD Differenz Feste Differenz Ausschalten Manueller Test Einschalten Anzugsmoment 2 5 Nm Nur Kup...

Page 14: ...Reklamation an gezeigt werden Die gleiche Empfehlung gilt f r die F lle in denen die Transportanweisungen nicht eingehalten wurden Bitte hinsichtlich der Lagerung die auf dem Verpackungskarton aufged...

Page 15: ...Hochdruckseite angeschlossen sein um alle Anlagenteile gut evakuieren zu k nnen Empfohlene Vorgehensweise 1 Nach Abschluss der Lecksuche 2 ist der Druck in der Anlage auf ein Vakuum von 500 mHg 0 67 m...

Page 16: ...st Verdichter baut keinen Druck auf Bitte kontrollieren ob etwaige in der Anlage befind lichen Bypassventile geschlossen sind Befinden sich s mtliche Magnetventile tats chlich in der gew nschten Stell...

Page 17: ...nd Filtertrockneraustausch sind solange zu wiederholen bis die Anlage sauber und s urefrei ist SindkeineAnzeichenvonS uremehrerkennbar sind die Burnout Eins tze in der Fl ssigkeitslei tung durch eine...

Page 18: ...15 Evaporating Temperature C R404A R507 Ambient Temperature C Temp rature ambiante C Temp rature d vaporation C 0 10 20 30 40 50 30 25 20 15 10 5 0 5 10 15 20 Evaporating Temperature C R134a Ambient T...

Page 19: ...0 15 10 5 0 5 Evaporating Temperature C R404A R507 Ambient Temperature C Temp rature ambiante C Temp rature d vaporation C 45 0 10 20 30 40 50 40 35 30 25 20 15 10 5 0 5 Evaporating Temperature C R452...

Page 20: ...Instructions 20 Danfoss DCS CC 2018 08 FRCC PI 059 A1 04 MOD LES UNE SEULE PHASE TROIS MODES DE PHASE...

Page 21: ...rentiel fixe Point de renclenchement Test manuel Point de declenchement Couple de serrage 20 Nm Fil de cuivre uniquement Point de renclenchement Reset manuel Reglage d usine Reset manuel Reset convert...

Page 22: ...sauxintemp ries et ou des substances corrosives ou inflammables 3 Mesures de s curit avant montage Toute op ration de montage et d entretien doit tre effectu e par un personnel qualifi confor m ment...

Page 23: ...vide Utilisez des raccords et flexibles de gros dia m tre et les connecter aux vannes d arr t plut t qu au raccord Schrader Cette mesure permet d viter des pertes de charge excessives Niveau d humidit...

Page 24: ...aude et le com presseur d clenchera sur la protection moteur Si cela se produit le r armement peut prendre deux trois heures Bruit de fonctionnement anormal v rifiez l absence de retour de liquide au...

Page 25: ...d huile et cartouches de filtre jusqu ce que le syst me soit propre et exempt de tout acide Quand il n y a plus aucune trace d acide remplacez les cartouches anti acides par le mod le standard et ret...

Page 26: ...Evaporating Temperature C R404A R507 Ambient Temperature C 35 0 10 20 30 40 50 30 25 20 15 10 5 0 5 10 15 Evaporating Temperature C R448A R449A Ambient Temperature C 35 0 10 20 30 40 50 30 25 20 15 1...

Page 27: ...nit length 45 0 10 20 30 40 50 40 35 30 25 20 15 10 5 0 5 Evaporating Temperature C R404A R507 Ambient Temperature C 45 0 10 20 30 40 50 40 35 30 25 20 15 10 5 0 5 Evaporating Temperature C R452A Ambi...

Page 28: ...Instrukcje 28 Danfoss DCS CC 2018 08 FRCC PI 059 A1 49 MODELE POJEDYNCZEJ FAZY MODELE TR JFAZOWE...

Page 29: ...17B 060 539366 060 539466 LP auto LP auto HP man HP auto Ci nienie za czania R nica Sta a r nica Ci nienie wy czania Sprawdzian manualny Ci nienie za czania Tightening torque 20 lb in Use copper wire...

Page 30: ...ni ej 35 C ani powy ej 50 C Nale y upewni si czy urz dzenie i jego opa kowanie nie jest nara one na bezpo rednie dzia anie deszczu czynnik w atwopalnych oraz czynnik w powoduj cych korozj 3 rodki bezp...

Page 31: ...wory odcinaj ce wchodz w sk ad instalacji agregat skraplaj cy musi by izolowany od uk adu Istotne jest r wnie pod czenie pompy pr niowej po obydwu stronach tj wysokie go i niskiego ci nienia aby odess...

Page 32: ...e y sprawdzi uzwojenia silnika przy pomocy omomie rza Uwaga W przypadku gdy wewn trzne zabez pieczenie silnika wy czy silnik spr arki mo e up yn kilka godzin zanim ponowny start spr arki b dzie mo liw...

Page 33: ...i gu cieczowym na zwyk y odwad niaj cy i w razie potrzeby usun wk ad z filtra na stronie ssawnej 14 Wskaz wki dla u ytkownika Wszystkie czynno ci serwisowe powinny by wykonywane tylko i wy cznie przez...

Page 34: ...its products without notice This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed All...

Reviews: