background image

Instructions

8 | © Danfoss | DCS (CC) | 2018.08

FRCC.PI.059.A1.02

9 - Verification before commissioning

 Ensure that all service valves are in the open 

position before start-up. A closed discharge or 
suction service valve may cause serious damage 
to the compressor and/or compromise safety 
device operation, thereby resulting in potential 
injury to personnel.
• Check that all safety devices are operational 
and properly set (safety pressure switch set 
point, mechanical relief valve if necessary, etc.). 
Make sure that these devices comply with both 
generally - and locally - applicable regulations 
and standards (e.g. EN 378-2:2016).

• When using high-pressure switches or relief 
valves, the setting must not exceed maximum 
service pressure of any system component. Re-
fer to the Application Guidelines for relevant 
condensing unit pressure safety limits.

• A low-pressure switch is recommended to 
prevent operation under vacuum. Use a mini-
mum setting of 1.2 bar (absolute).

• Verify that all electrical connections are proper-
ly fastened and in compliance with local safety 
regulations.

• A compressor crankcase heater is factory ins-
talled, ensure that it has been energized for a 
minimum of 12 hours before initial start-up and/
or during prolonged shutdown periods.

10 - Start up

 Never start the compressor in the absence of 

a refrigerant charge. 

• Do not bypass the LP or any other safety swit-
ches during start-up

• Check current draw and voltage levels.

• Monitor the oil sight glass to ensure proper oil 
return to the compressor.After 2 to 4 hours of 
operations under established conditions, check 
the oil level and add oil if necessary (refer to TI 
bulletin 3-025).
If oil return continues to perform poorly, further 
investigation of the piping design is required. 

• In all cases, the application limits of the compressor 
must be respected; moreover, high superheat values 
lead to high discharge temperatures and decrease 
compressor capacity. The maximum discharge tem-
perature is 130°C: operating at a higher temperature 
may result in refrigerant decomposition.

• Under steady-state operating conditions, check 
refrigerant piping or capillary tubes for abnor-
mal vibrations (refrigeration line movement in 
excess of 1.5 mm necessitates corrective actions, 
pipe brackets, etc.).

• Ensure that refrigerant flow through the liquid 
line sight glass (when mounted) is adequate and 
that operating temperatures correspond with 
system specifications.

• When needed, refrigerant may be added in the 
liquid phase, carefully throttling the refrigerant 
on the low-pressure side and as far as possible 
from the compressor.The compressor must be 
operating during this process.

 Do not overcharge the system.

11 - Troubleshooting

• 

Compressor failure to start:

 verify that the 

compressor is hooked up to the power supply; 
check the power lead connections and all sui-
table capacitors on single-phase models. If these 
verifications reveal no abnormality, control the 
motor windings with an ohmmeter. 

Note: when the internal motor protector has 
tripped out, it may take up to several hours to 
reset and restart the compressor.

• Compressor failure to build up pressure:

 

check to make sure that all bypass valves in the 
system have not been opened. Also check that 
all solenoid valves are in their proper position. 
If the internal pressure relief valve is open, the 
compressor sump will be warm and the com-
pressor will trip out on the motor protector. If 
this happens, it may take up to 2 or 3 hours to 
reset and automatically restart the compressor.

• Abnormal running noise on the system: 

  - Ensure the absence of any liquid flood-back 
to the compressor by means of measuring the 
return gas superheat and compressor sump 
temperature. The sump should be at least 10K 
above the saturated suction temperature under 
steady-state operating conditions.
  - Check that the fans are running free and wit-
hout vibration.

• The high-pressure switch trips out:

 check 

condenser operations (condenser cleanliness, 
fan operations, etc.). If above check out OK, the 
problem may be due to either refrigerant over-
charging or the presence of a non-condensable 
(e.g. air, moisture) in the circuit. 

• The low-pressure switch trips out:

 check eva-

porator operations (coil cleanliness, fan opera-
tions, water flow, water filter, etc.), liquid refrige-
rant flow and pressure drops (solenoid valve, filter 
dryer, expansion valve, etc.), refrigerant charge.

• Low refrigerant charge:

 the correct refrige-

rant charge is given by the liquid sight glass 
indication, the condenser delta T in relation to 
the refrigerant pressure tables (pressure-tempe-
rature), the superheat and the sub-cooling, etc. 
(if additional charge is deemed necessary, refer 
to the 

«Filling the system»

 section). 

• Compressor maximum short cycling: 

there 

must be a minimum delay of five minutes 
between two compressor starts. DCC recom-
mends the compressor should run at least two 
minutes after each start, and between each stop 
and start must be three minutes standstill. Only 
during pump down cycle, the compressor may 
run much shorter until the pumpdown pressure 
has been reached or when safety devices will 
prohibit compressor further operation.

12 - Maintenance

• Proper operations and maintenance of the 
condensing units serve to prevent against sys-
tem-related problems.The following preventive 
maintenance checks, to be performed at regular 
intervals, are highly recommended:

  - Control operating conditions (evaporating 
temperature, condensing temperature, com-
pressor discharge temperature, temperature 
difference on heat exchangers, superheat, 
sub-cooling). These conditions must always re-
main within compressor operation limits.
  - Verify that safety devices are operational and 
properly set.

  - Check the compressor oil level and quality; 
this step may include an acid test, humidity 
check, spectrometer analysis, etc. whenever the 
oil becomes discolored.
  - Ensure that the circuit is leak tight.

  - Verify the proper operation of heat exchan-
gers and, if necessary, clean them.
  - Check that the fans are running free (without 
vibration) and current draw on the compressor 
motor as well as proper voltage balance between 
phases.
  - Note 1: The condenser must be checked at 
least once a year for clogging and be cleaned if 
deemed necessary. Access to the internal side of 
the condenser takes place through the fan pa-
nel.
Microchannel coils tend to accumulate dirt on 
the surface rather than inside, which makes 
them easier to clean than fin-&-tube coils.
  - Change the filter dryer when necessary.
  - Check that all electrical connections are still 
adequately fastened. 
  - Make sure the condensing unit is clean and 
in good working order; verify the absence of rust 
or corrosion on components under pressure and 
electrical connections. 
  - Make sure the refrigerant charge is suitable 
for both winter and summer operation.
• Ensure that periodic in-service inspections re-
quired by local regulations are performed. 
  - Note 2: Remove surface dirt, leaves, fibers, 
etc. with a vacuum cleaner, equipped with a 
brush or other soft attachment. Alternatively, 
blow compressed air through the coil from the 
inside out, and brush with a soft bristle.
Do not use a wire brush. Do not impact or scrape 
the coil with the vacuum tube or air nozzle.

13 - Replacement

 Precaution must be taken when disconnec-

ting any components, cutting or drilling holes in 
the tubing to ensure that no refrigerant under 
pressure is present in the system.

 The refrigerant shall not be discharged direc-

tly into the atmosphere; rather, it must be remo-
ved using approved reclamation techniques and 
equipment and then safely stored, inaccordance 
with applicable legislation.

 The presence of refrigerant vapor can displace 

air and lead to suffocation. Proper ventilation is 
mandatory at all times when servicing the equip-
ment.

 A condensing unit component change must be 

carried out in compliance with local regulations.

• Make sure that the main power supply has 
been switched off.

• Before replacement, it is necessary to deter-
mine the cause of failure and implement reme-
dial action. If such analysis and repair are not 

Summary of Contents for Optyma OP-MCRN030

Page 1: ...Instructions Condensing Units Optyma Integralrange Danfoss DCS CC 2018 08 FRCC PI 059 A1 ML 1 English English p 2 Deutsch German p 10 Fran ais French p 18 Polski Polish p 26...

Page 2: ...N108 OP LGQN136 NTZ096 NTZ108 NTZ136 693 5 1500 870 OP LGQN215 OP LGQN271 NTZ215 NTZ271 836 5 1500 870 35 0 10 20 30 40 50 30 25 20 15 10 5 0 5 10 15 Evaporating Temperature C R404A R507 Ambient Tempe...

Page 3: ...clearance 2 x unit length Fig 2 Fig 3 Fig 4 45 0 10 20 30 40 50 40 35 30 25 20 15 10 5 0 5 Evaporating Temperature C R404A R507 Ambient Temperature C 45 0 10 20 30 40 50 40 35 30 25 20 15 10 5 0 5 Eva...

Page 4: ...Instructions 4 Danfoss DCS CC 2018 08 FRCC PI 059 A1 02 SINGLE PHASE MODELS THREE PHASE MODELS...

Page 5: ...Instructions Danfoss DCS CC 2018 08 5 FRCC PI 059 A1 02 For R404A models Factory setting HP bar MBP 28 8 LBP 28 3 LP bar...

Page 6: ...stored in an ambient temperature of below 35 C 31 F or above 50 C 122 F Ensure that the condensing unit and its packa ging are not exposed to rain and or a corrosive flammable atmosphere 3 Safety meas...

Page 7: ...if necessary Vacuum pump A two stage vacuum pump with gas ballast valve 0 04 mbar standing vacuum shall be used its capacity is to be consistent with system volume Never use the compressor as a vacuu...

Page 8: ...perations condenser cleanliness fan operations etc If above check out OK the problem may be due to either refrigerant over charging or the presence of a non condensable e g air moisture in the circuit...

Page 9: ...nit tubing and compressor surface temperatures may exceed 100 C 212 F and cause severe bodily burns Special precau tion must be taken when working around the compressor and refrigerant tubing Moreover...

Page 10: ...0 5 10 15 Evaporating Temperature C R404A R507 Ambient Temperature C Umgebungstemperatur C Verdampfungstemperatur C 35 0 10 20 30 40 50 30 25 20 15 10 5 0 5 10 15 Evaporating Temperature C R448A R449A...

Page 11: ...Temperature C R404A R507 Ambient Temperature C Umgebungstemperatur C Verdampfungstemperatur C 45 0 10 20 30 40 50 40 35 30 25 20 15 10 5 0 5 Evaporating Temperature C R452A Ambient Temperature C Umge...

Page 12: ...Instruktion 12 Danfoss DCS CC 2018 08 FRCC PI 059 A1 03 EINPHASIGE MODELLE DREI PHASEN MODELLE...

Page 13: ...n Hg KP 15 15A 17W 17B KP17W B 060 539366 060 539466 ND auto ND auto HD man HD auto Einschalten ND HD ND HD Differenz Feste Differenz Ausschalten Manueller Test Einschalten Anzugsmoment 2 5 Nm Nur Kup...

Page 14: ...Reklamation an gezeigt werden Die gleiche Empfehlung gilt f r die F lle in denen die Transportanweisungen nicht eingehalten wurden Bitte hinsichtlich der Lagerung die auf dem Verpackungskarton aufged...

Page 15: ...Hochdruckseite angeschlossen sein um alle Anlagenteile gut evakuieren zu k nnen Empfohlene Vorgehensweise 1 Nach Abschluss der Lecksuche 2 ist der Druck in der Anlage auf ein Vakuum von 500 mHg 0 67 m...

Page 16: ...st Verdichter baut keinen Druck auf Bitte kontrollieren ob etwaige in der Anlage befind lichen Bypassventile geschlossen sind Befinden sich s mtliche Magnetventile tats chlich in der gew nschten Stell...

Page 17: ...nd Filtertrockneraustausch sind solange zu wiederholen bis die Anlage sauber und s urefrei ist SindkeineAnzeichenvonS uremehrerkennbar sind die Burnout Eins tze in der Fl ssigkeitslei tung durch eine...

Page 18: ...15 Evaporating Temperature C R404A R507 Ambient Temperature C Temp rature ambiante C Temp rature d vaporation C 0 10 20 30 40 50 30 25 20 15 10 5 0 5 10 15 20 Evaporating Temperature C R134a Ambient T...

Page 19: ...0 15 10 5 0 5 Evaporating Temperature C R404A R507 Ambient Temperature C Temp rature ambiante C Temp rature d vaporation C 45 0 10 20 30 40 50 40 35 30 25 20 15 10 5 0 5 Evaporating Temperature C R452...

Page 20: ...Instructions 20 Danfoss DCS CC 2018 08 FRCC PI 059 A1 04 MOD LES UNE SEULE PHASE TROIS MODES DE PHASE...

Page 21: ...rentiel fixe Point de renclenchement Test manuel Point de declenchement Couple de serrage 20 Nm Fil de cuivre uniquement Point de renclenchement Reset manuel Reglage d usine Reset manuel Reset convert...

Page 22: ...sauxintemp ries et ou des substances corrosives ou inflammables 3 Mesures de s curit avant montage Toute op ration de montage et d entretien doit tre effectu e par un personnel qualifi confor m ment...

Page 23: ...vide Utilisez des raccords et flexibles de gros dia m tre et les connecter aux vannes d arr t plut t qu au raccord Schrader Cette mesure permet d viter des pertes de charge excessives Niveau d humidit...

Page 24: ...aude et le com presseur d clenchera sur la protection moteur Si cela se produit le r armement peut prendre deux trois heures Bruit de fonctionnement anormal v rifiez l absence de retour de liquide au...

Page 25: ...d huile et cartouches de filtre jusqu ce que le syst me soit propre et exempt de tout acide Quand il n y a plus aucune trace d acide remplacez les cartouches anti acides par le mod le standard et ret...

Page 26: ...Evaporating Temperature C R404A R507 Ambient Temperature C 35 0 10 20 30 40 50 30 25 20 15 10 5 0 5 10 15 Evaporating Temperature C R448A R449A Ambient Temperature C 35 0 10 20 30 40 50 30 25 20 15 1...

Page 27: ...nit length 45 0 10 20 30 40 50 40 35 30 25 20 15 10 5 0 5 Evaporating Temperature C R404A R507 Ambient Temperature C 45 0 10 20 30 40 50 40 35 30 25 20 15 10 5 0 5 Evaporating Temperature C R452A Ambi...

Page 28: ...Instrukcje 28 Danfoss DCS CC 2018 08 FRCC PI 059 A1 49 MODELE POJEDYNCZEJ FAZY MODELE TR JFAZOWE...

Page 29: ...17B 060 539366 060 539466 LP auto LP auto HP man HP auto Ci nienie za czania R nica Sta a r nica Ci nienie wy czania Sprawdzian manualny Ci nienie za czania Tightening torque 20 lb in Use copper wire...

Page 30: ...ni ej 35 C ani powy ej 50 C Nale y upewni si czy urz dzenie i jego opa kowanie nie jest nara one na bezpo rednie dzia anie deszczu czynnik w atwopalnych oraz czynnik w powoduj cych korozj 3 rodki bezp...

Page 31: ...wory odcinaj ce wchodz w sk ad instalacji agregat skraplaj cy musi by izolowany od uk adu Istotne jest r wnie pod czenie pompy pr niowej po obydwu stronach tj wysokie go i niskiego ci nienia aby odess...

Page 32: ...e y sprawdzi uzwojenia silnika przy pomocy omomie rza Uwaga W przypadku gdy wewn trzne zabez pieczenie silnika wy czy silnik spr arki mo e up yn kilka godzin zanim ponowny start spr arki b dzie mo liw...

Page 33: ...i gu cieczowym na zwyk y odwad niaj cy i w razie potrzeby usun wk ad z filtra na stronie ssawnej 14 Wskaz wki dla u ytkownika Wszystkie czynno ci serwisowe powinny by wykonywane tylko i wy cznie przez...

Page 34: ...its products without notice This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed All...

Reviews: