Instructions

Condensing Units

 

Optyma

 

Integral 

range

© Danfoss | DCS (CC) | 2018.08

FRCC.PI.059.A1.ML | 1

English / English

p. 2

Deutsch / German

p. 10

Français / French

p. 18

Polski / Polish

p. 26

Summary of Contents for Optyma OP-MCRN030

Page 1: ...Instructions Condensing Units Optyma Integralrange Danfoss DCS CC 2018 08 FRCC PI 059 A1 ML 1 English English p 2 Deutsch German p 10 Fran ais French p 18 Polski Polish p 26...

Page 2: ...N108 OP LGQN136 NTZ096 NTZ108 NTZ136 693 5 1500 870 OP LGQN215 OP LGQN271 NTZ215 NTZ271 836 5 1500 870 35 0 10 20 30 40 50 30 25 20 15 10 5 0 5 10 15 Evaporating Temperature C R404A R507 Ambient Tempe...

Page 3: ...clearance 2 x unit length Fig 2 Fig 3 Fig 4 45 0 10 20 30 40 50 40 35 30 25 20 15 10 5 0 5 Evaporating Temperature C R404A R507 Ambient Temperature C 45 0 10 20 30 40 50 40 35 30 25 20 15 10 5 0 5 Eva...

Page 4: ...Instructions 4 Danfoss DCS CC 2018 08 FRCC PI 059 A1 02 SINGLE PHASE MODELS THREE PHASE MODELS...

Page 5: ...Instructions Danfoss DCS CC 2018 08 5 FRCC PI 059 A1 02 For R404A models Factory setting HP bar MBP 28 8 LBP 28 3 LP bar...

Page 6: ...stored in an ambient temperature of below 35 C 31 F or above 50 C 122 F Ensure that the condensing unit and its packa ging are not exposed to rain and or a corrosive flammable atmosphere 3 Safety meas...

Page 7: ...if necessary Vacuum pump A two stage vacuum pump with gas ballast valve 0 04 mbar standing vacuum shall be used its capacity is to be consistent with system volume Never use the compressor as a vacuu...

Page 8: ...perations condenser cleanliness fan operations etc If above check out OK the problem may be due to either refrigerant over charging or the presence of a non condensable e g air moisture in the circuit...

Page 9: ...nit tubing and compressor surface temperatures may exceed 100 C 212 F and cause severe bodily burns Special precau tion must be taken when working around the compressor and refrigerant tubing Moreover...

Page 10: ...0 5 10 15 Evaporating Temperature C R404A R507 Ambient Temperature C Umgebungstemperatur C Verdampfungstemperatur C 35 0 10 20 30 40 50 30 25 20 15 10 5 0 5 10 15 Evaporating Temperature C R448A R449A...

Page 11: ...Temperature C R404A R507 Ambient Temperature C Umgebungstemperatur C Verdampfungstemperatur C 45 0 10 20 30 40 50 40 35 30 25 20 15 10 5 0 5 Evaporating Temperature C R452A Ambient Temperature C Umge...

Page 12: ...Instruktion 12 Danfoss DCS CC 2018 08 FRCC PI 059 A1 03 EINPHASIGE MODELLE DREI PHASEN MODELLE...

Page 13: ...n Hg KP 15 15A 17W 17B KP17W B 060 539366 060 539466 ND auto ND auto HD man HD auto Einschalten ND HD ND HD Differenz Feste Differenz Ausschalten Manueller Test Einschalten Anzugsmoment 2 5 Nm Nur Kup...

Page 14: ...Reklamation an gezeigt werden Die gleiche Empfehlung gilt f r die F lle in denen die Transportanweisungen nicht eingehalten wurden Bitte hinsichtlich der Lagerung die auf dem Verpackungskarton aufged...

Page 15: ...Hochdruckseite angeschlossen sein um alle Anlagenteile gut evakuieren zu k nnen Empfohlene Vorgehensweise 1 Nach Abschluss der Lecksuche 2 ist der Druck in der Anlage auf ein Vakuum von 500 mHg 0 67 m...

Page 16: ...st Verdichter baut keinen Druck auf Bitte kontrollieren ob etwaige in der Anlage befind lichen Bypassventile geschlossen sind Befinden sich s mtliche Magnetventile tats chlich in der gew nschten Stell...

Page 17: ...nd Filtertrockneraustausch sind solange zu wiederholen bis die Anlage sauber und s urefrei ist SindkeineAnzeichenvonS uremehrerkennbar sind die Burnout Eins tze in der Fl ssigkeitslei tung durch eine...

Page 18: ...15 Evaporating Temperature C R404A R507 Ambient Temperature C Temp rature ambiante C Temp rature d vaporation C 0 10 20 30 40 50 30 25 20 15 10 5 0 5 10 15 20 Evaporating Temperature C R134a Ambient T...

Page 19: ...0 15 10 5 0 5 Evaporating Temperature C R404A R507 Ambient Temperature C Temp rature ambiante C Temp rature d vaporation C 45 0 10 20 30 40 50 40 35 30 25 20 15 10 5 0 5 Evaporating Temperature C R452...

Page 20: ...Instructions 20 Danfoss DCS CC 2018 08 FRCC PI 059 A1 04 MOD LES UNE SEULE PHASE TROIS MODES DE PHASE...

Page 21: ...rentiel fixe Point de renclenchement Test manuel Point de declenchement Couple de serrage 20 Nm Fil de cuivre uniquement Point de renclenchement Reset manuel Reglage d usine Reset manuel Reset convert...

Page 22: ...sauxintemp ries et ou des substances corrosives ou inflammables 3 Mesures de s curit avant montage Toute op ration de montage et d entretien doit tre effectu e par un personnel qualifi confor m ment...

Page 23: ...vide Utilisez des raccords et flexibles de gros dia m tre et les connecter aux vannes d arr t plut t qu au raccord Schrader Cette mesure permet d viter des pertes de charge excessives Niveau d humidit...

Page 24: ...aude et le com presseur d clenchera sur la protection moteur Si cela se produit le r armement peut prendre deux trois heures Bruit de fonctionnement anormal v rifiez l absence de retour de liquide au...

Page 25: ...d huile et cartouches de filtre jusqu ce que le syst me soit propre et exempt de tout acide Quand il n y a plus aucune trace d acide remplacez les cartouches anti acides par le mod le standard et ret...

Page 26: ...Evaporating Temperature C R404A R507 Ambient Temperature C 35 0 10 20 30 40 50 30 25 20 15 10 5 0 5 10 15 Evaporating Temperature C R448A R449A Ambient Temperature C 35 0 10 20 30 40 50 30 25 20 15 1...

Page 27: ...nit length 45 0 10 20 30 40 50 40 35 30 25 20 15 10 5 0 5 Evaporating Temperature C R404A R507 Ambient Temperature C 45 0 10 20 30 40 50 40 35 30 25 20 15 10 5 0 5 Evaporating Temperature C R452A Ambi...

Page 28: ...Instrukcje 28 Danfoss DCS CC 2018 08 FRCC PI 059 A1 49 MODELE POJEDYNCZEJ FAZY MODELE TR JFAZOWE...

Page 29: ...17B 060 539366 060 539466 LP auto LP auto HP man HP auto Ci nienie za czania R nica Sta a r nica Ci nienie wy czania Sprawdzian manualny Ci nienie za czania Tightening torque 20 lb in Use copper wire...

Page 30: ...ni ej 35 C ani powy ej 50 C Nale y upewni si czy urz dzenie i jego opa kowanie nie jest nara one na bezpo rednie dzia anie deszczu czynnik w atwopalnych oraz czynnik w powoduj cych korozj 3 rodki bezp...

Page 31: ...wory odcinaj ce wchodz w sk ad instalacji agregat skraplaj cy musi by izolowany od uk adu Istotne jest r wnie pod czenie pompy pr niowej po obydwu stronach tj wysokie go i niskiego ci nienia aby odess...

Page 32: ...e y sprawdzi uzwojenia silnika przy pomocy omomie rza Uwaga W przypadku gdy wewn trzne zabez pieczenie silnika wy czy silnik spr arki mo e up yn kilka godzin zanim ponowny start spr arki b dzie mo liw...

Page 33: ...i gu cieczowym na zwyk y odwad niaj cy i w razie potrzeby usun wk ad z filtra na stronie ssawnej 14 Wskaz wki dla u ytkownika Wszystkie czynno ci serwisowe powinny by wykonywane tylko i wy cznie przez...

Page 34: ...its products without notice This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed All...