troller is active. The FC 300 is in the “Not
ready” state when:
-
It has an alarm
-
It is in local mode
-
Local LCP stop is activated
Error 114
Too many loops
Too many nested loops exist in the executed
program.
Error 115
Par. Save failed
Saving of the option parameter failed.
Error 116
Param. memory
The parameters in EEPROM are no longer cor-
rect because of
-
EEPROM defective or
-
Power outage while saving
NB!
You have to re-initialise the pa-
rameter with a 14-22 Reset and
then overwrite these parame-
ters again with your own appli-
cation parameters.
Otherwise motion programs which require ap-
plication parameters will no longer function
correctly.
Error 117
Progr. Memory
The program data stored in EEPROM cannot
be found or are no longer correct because of
-
EEPROM defective or
-
Power outage while saving
You have to do a 3-finger reset to reset all
parameters to their defaults (ex factory) and
to delete all user programs, arrays, and appli-
cation parameters.
Afterwards re-load the programs and param-
eters.
This corresponds to the
→
Erase Option EE-
PROM
or a
→
Reset complete
in the APOSS
menu.
Error 118
Reset by CPU
The processor has been stopped and a re-set
has automatically been executed (watchdog).
Causes could be:
-
Short term voltage drop
-
Voltage peak, or
-
Short circuit
Error 119
User abort
The
Autostart
program has been aborted by
the user.
Or the [CANCEL] key was pressed during
switching on and a Master Reset triggered.
Error 125
HW end limit
A motion command has caused an axis limit
switch to be activated.
Through activation of an end limit switch, the
controller (depending on the par. 33-40
be-
haviour at End Limit Switch
) is automatically
switched off and the drive must be manually
moved out of this position, before the error
message can be cleared.
Error 149
Too many inter.
More interrupt functions than the maximum
possible number were used. Permitted are:
32 ON INT
32 ON STATBIT
32 ON COMBIT
10 ON PARAM
20 ON APOS, ON MAPOS, ON MCPOS
Error 150
No ext. 24V
External supply is missing.
Error 151
Too many gosub
In the program exists too many calls from one
subroutine to another subroutine.
The error usually occurs when there is a re-
current reference to one of the subprograms
in a subprogram.
Avoid too many (10 is maximum) opposing
subroutine calls, and avoid subroutines which
call themselves (re-cursive subroutine proce-
dures).