Illustration 4.3: Up/down factor with speed synchronisation
4.2.3. Hold Function
The Hold function operates the slave drive in closed loop speed control at a speed independent
of the master. With par. 19-02
Hold function
you can choose whether the slave is to run at a fixed
speed set in par. 19-03 or whether it is to maintain current speed. For the duration of the Hold
signal, the speed of the master is no longer taken into account; the master can even stop without
this having any effect on the slave drive. While the Hold function is activated you can change the
speed with inputs 32 and 33. The speed is changing according to the settings in par. 19-04
Delta
hold speed
and par. 19-12
Step width
.
Syncronising Controller MCO 350 Operating
Instructions
4. Synchronisation