If
[1] Serial communication
is selected, commands are
activated only when given via serial communication.
Terminal
Bit 02/03/04
Function
0
0
Stop/Anti-clockwise
0
1
Start/Clockwise
1
0
Stop/Anti-clockwise
1
1
Start/Clockwise
Table 9.9 [1] Serial Communication
If
[2] Logic AND
is selected, both signals must be activated
to perform the function.
Terminal
Bit 02/03/04
Function
0
0
Stop/Anti-clockwise
0
1
Stop/Anti-clockwise
1
0
Stop/Anti-clockwise
1
1
Start/Clockwise
Table 9.10 [2] Logic AND
If
[3] Logic OR
is selected, activation of one signal activates
the function.
Terminal
Bit 02/03/04
Function
0
0
Stop/Anti-clockwise
0
1
Start/Clockwise
1
0
Start/Clockwise
1
1
Start/Clockwise
Table 9.11 [3] Logic OR
The effect of control mode upon the function of
8-55 Set-
up Select
and
8-56 Preset Reference Select
:
If
[0] Digital input
is selected, the terminals control the set-
up and preset reference functions.
Terminal
Bit 00/01, 13/14 Function
Msb
Lsb
Msb
Lsb
Preset ref. Set-up no.
0
0
0
0
1
0
0
0
1
1
0
0
1
0
1
0
0
1
1
1
0
1
0
0
2
0
1
0
1
2
0
1
1
0
2
0
1
1
1
2
1
0
0
0
3
1
0
0
1
3
1
0
1
0
3
1
0
1
1
3
1
1
0
0
4
1
1
0
1
4
1
1
1
0
4
1
1
1
1
4
Table 9.12 [0] Digital Input
If
[1] Serial communication
is selected, commands are
activated only when given via serial communication.
Terminal
Bit 00/01, 13/14 Function
Msb
Lsb
Msb
Lsb
Preset ref. Set-up no.
0
0
0
0
1
0
0
0
1
2
0
0
1
0
3
0
0
1
1
4
0
1
0
0
1
0
1
0
1
2
0
1
1
0
3
0
1
1
1
4
1
0
0
0
1
1
0
0
1
2
1
0
1
0
3
1
0
1
1
4
1
1
0
0
1
1
1
0
1
2
1
1
1
0
3
1
1
1
1
4
Table 9.13 [1] Serial Communication
If
[2] Logic AND
is selected, both signals must be activated
to perform the function.
Troubleshooting
MCA 123 POWERLINK Operating Instructions
48
MG92C102 - VLT
®
is a registered Danfoss trademark
9