12-12 Auto Negotiation
Option: Function:
[1] On
NOTE
In POWERLINK this parameter is fixed to OFF setting.
12-13 Link Speed
Option:
Function:
Forces the link speed for each port in 10 Mbps or
100 Mbps. If
12-12 Auto Negotiation
is set to: ON,
this parameter is read only and displays the
actual link speed. If no link is present, “None” is
displayed.
[0] None
[1] 10 Mbps
[2] 100 Mbps
NOTE
In POWERLINK this parameter is locked to 100 Mbs.
12-14 Link Duplex
Option:
Function:
Forces the duplex for each port to Full or Half
duplex. If
12-12 Auto Negotiation
is set to: [ON],
this parameter is read only.
[0] Half Duplex
[1] Full Duplex
NOTE
In POWERLINK this parameter is locked to half duplex.
7.2.3 12-2* Process Data
12-20 Control Instance
Range:
Function:
[None, 20,
21, 23, 100,
101, 103]
Read only. Displays the connection to the
master. In Ethernet/IP: If no CIP connection is
present, “None” is displayed. In EtherCAT: If no
connection is active "None" is displayed, else it
displays the active PDO. In POWERLINK: If no
connection is active “None” is displayed, else it
displays the active PDO (23).
12-21 Process Data Config Write
Range:
Function:
[[0 - 9] PCD read 0 - 9] Configuration of readable process
data.
In POWERLINK this parameter is read only. Same applies
for
12-22 Process Data Config Read
,
12-23 Process Data
Config Write Size
and
12-24 Process Data Config Read Size
.
12-22 Process Data Config Read
Range:
Function:
[[0 - 9] PCD read 0 - 9] Configuration of readable process
data.
12-23 Process Data Config Write Size
Range:
Function:
16
*
[8 - 32 ] Sets the number of bits being sent from the
frequency converter as process data. The setting
counts from right (LSB). The value 1 means that
only the least significant bit of the signal is
transferred from the frequency converter.
12-24 Process Data Config Read Size
Range:
Function:
16
*
[8 - 32 ] Sets the number of bits being sent to the
frequency converter as process data. The setting
counts from right (LSB). The value 1 means that
only the least significant bit of the signal is
transferred to the frequency converter. The
preceding bits are set to zero.
12-28 Store Data Values
Option:
Function:
[0]
Off
[1]
Store all setups
[2]
Store all setups
12-29 Store Always
Option: Function:
Activates function that always stores received
parameter data in non-volatile memory (EEPROM).
[0]
*
Off
[1]
On
7.2.4 12-6* Ethernet PowerLink
12-60 Node ID
Range:
Function:
1
*
[1 -
239 ]
Enter the Node ID in this parameter or alterna-
tively in the hardware switch. In order to adjust
the Node ID in
12-60 Node ID
, the hardware switch
must be set to o or 254 (i.e. all switches set to
[ON] or to [OFF]). Otherwise this parameter
displays the actual setting of the switch. Setting
this parameter will first be active at the next
power up cycle.
12-62 SDO Timeout
Range:
Function:
30000
ms
*
[0 - 2000000000
ms]
12-62 SDO Timeout
is the SDO
Timeout in milliseconds. Value of
this parameter is read during
Parameters
MCA 123 POWERLINK Operating Instructions
38
MG92C102 - VLT
®
is a registered Danfoss trademark