8-13 Configurable Status Word STW
Option:
Function:
“1” indicates that the terminal is high
[13] T29 DI
status.
The bit indicates the status of terminal 29.
“0” indicates that the terminal is low
“1” indicates that the terminal is high
[14] T32 DI
status.
The bit indicates the status of terminal 32.
“0” indicates that the terminal is low
“1” indicates that the terminal is high
[15] T33 DI
status.
The bit indicates the status of terminal 33.
“0” indicates that the terminal is low
“1” indicates that the terminal is high
[16] T37 DI
status
The bit indicates the status of terminal 37.
0” indicates T37 is low (safe stop)
“1” indicates T37 is high (normal)
[21] Thermal
warning
The thermal warning turns on when the
temperature exceeds the limit in the motor,
the frequency converter, the brake resistor, or
the thermistor.
[30] Brake fault
(IGBT)
Output is Logic ‘1’ when the brake IGBT is
short-circuited. Use this function to protect
the frequency converter if there is a fault on
the brake modules. Use the output/relay to
cut out the main voltage from the frequency
converter.
[40] Out of ref.
range
[60] Comtor 0
See parameter group
13-1* ComparatorsCom-
parators
. If Comtor 0 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[61] Comtor 1
See parameter group
13-1* ComparatorsCom-
parators
. If Comtor 1 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[62] Comtor 2
See parameter group
13-1* ComparatorsCom-
parators
. If Comtor 2 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[63] Comtor 3
See parameter group
13-1* ComparatorsCom-
parators
. If Comtor 3 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[64] Comtor 4
See parameter group
13-1* ComparatorsCom-
parators
. If Comtor 4 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[65] Comtor 5
See parameter group
13-1* ComparatorsCom-
parators
. If Comtor 5 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[70] Logic Rule
0
See parameter group
13-4* LC-4# Logic
RulesLogic Rules
. If Logic Rule 0 is evaluated as
TRUE, the output goes high. Otherwise, it is
low.
[71] Logic Rule
1
See parameter group
13-4* LC-4# Logic
RulesLogic Rules
. If Logic Rule 1 is evaluated as
TRUE, the output goes high. Otherwise, it is
low.
[72] Logic Rule
2
See parameter group
13-4* LC-4# Logic
RulesLogic Rules
. If Logic Rule 2 is evaluated as
8-13 Configurable Status Word STW
Option:
Function:
TRUE, the output goes high. Otherwise, it is
low.
[73] Logic Rule
3
See parameter group 13-4*. If Logic Rule 3 is
evaluated as TRUE, the output goes high.
Otherwise, it is low.
[74] Logic Rule
4
See parameter group
13-4* LC-4# Logic
RulesLogic Rules
. If Logic Rule 4 is evaluated as
TRUE, the output goes high. Otherwise, it is
low.
[75] Logic Rule
5
See parameter group
13-4* LC-4# Logic
RulesLogic Rules
. If Logic Rule 5 is evaluated as
TRUE, the output goes high. Otherwise, it is
low.
[80] SL Digital
Output A
See
13-52 SL Controller Action
. The output
goes high whenever the Smart Logic Action
[38] Set digital out A high
is executed. The
output goes low whenever the Smart Logic
Action
[32] Set digital out A low
is executed.
[81] SL Digital
Output B
See
13-52 SL Controller Action
. The input goes
high whenever the Smart Logic Action
[39]
Set digital out B high
is executed. The input
goes low whenever the Smart Logic Action
[33] Set digital out B low
is executed.
[82] SL Digital
Output C
See
13-52 SL Controller Action
. The input goes
high whenever the Smart Logic Action
[40]
Set digital out C high
is executed. The input
goes low whenever the Smart Logic Action
[34] Set digital out C low
is executed.
[83] SL Digital
Output D
See
13-52 SL Controller Action
. The input goes
high whenever the Smart Logic Action
[41]
Set digital out D high
is executed. The input
goes low whenever the Smart Logic Action
[35] Set digital out D low
is executed.
[84] SL Digital
Output E
See
13-52 SL Controller Action
. The input goes
high whenever the Smart Logic Action
[42]
Set digital out E high
is executed. The input
goes low whenever the Smart Logic Action
[36] Set digital out E low
is executed.
[85] SL Digital
Output F
See
13-52 SL Controller Action
. The input goes
high whenever the Smart Logic Action
[43]
Set digital out F high
is executed. The input
goes low whenever the Smart Logic Action
[37] Set digital out F low
is executed.
8-14 Configurable Control Word CTW
Option:
Function:
Selection of control word bit 10 if it is active
low or active high.
[0] None
[1] Profile default
[2] CTW Valid,
active low
[3] Safe Option
Reset
Parameters
MCA 123 POWERLINK Operating Instructions
MG92C102 - VLT
®
is a registered Danfoss trademark
35