12-62 SDO Timeout
Range:
Function:
communication initialization into
Object 1300h
12-63 Basic Ethernet Timeout
Range:
Function:
5000.000
ms
*
[0 -
2100000
ms]
12-63 Basic Ethernet Timeout
in
microseconds. This parameter is
mapped to Object 1F99h. If the
POWERLINK interface does not receive
a SoC frame within the specified
period of time, the interface shifts to
standard Ethernet mode. This feature
is first available from version 2.00 of
the POWERLINK Interface.
12-66 Threshold
Range:
Function:
15
*
[0 -
99999 ]
12-66 Threshold
holds six threshold values. If
one of these thresholds are exceeded, the
POWERLINK Interface exits operational mode.
The parameters are set to optimal settings and
should not be changed. The actual value of
the counters can be read out via
12-67 Threshold Counters
.
12-67 Threshold Counters
Range:
Function:
0
*
[0 -
65538 ]
12-67 Threshold Counters
hold 6 counters. The
counter reflects the actual value in the
POWERLINK interface. Counters increases with a
count of eight at detection of an error and
decreases with a count of one when no errors
are detected. The values are read only.
12-68 Cumulative Counters
Range:
Function:
0
*
[0 - 65535 ] Loss off SoC Cumulative. This parameter
reflects the value in object 1C0Bh, subindex 1.
12-69 Ethernet PowerLink Status
Range:
Function:
0
*
[0 - 4294967295 ]
7.2.5 12-8* Other Ethernet Services
12-80 FTP Server
Option:
Function:
[0]
Disabled
Disables the built-in FTP server.
[1]
Enabled
Enables the built-in FTP server.
12-81 HTTP Server
Option:
Function:
[0]
Disabled
[1]
Enabled
Enables the built-in HTTP (web) server.
12-82 SMTP Service
Option:
Function:
[0] Disabled
[1] Enabled
Enables the SMTP (e-mail) service on the option.
12-89 Transparent Socket Channel Port
Range:
Function:
Size
related
*
[ 0 -
0. ]
Configures the TCP port number for the
transparent socket channel. This configu-
ration enables FC telegrams to be sent
transparently on Ethernet via TCP. Default
value is 4000, 0 means disabled. The MCT
10 Set-up Software uses this port.
7.2.6 12-9* Advanced Ethernet Settings
12-90 Cable Diagnostic
Option:
Function:
Enables/disables advanced Cable diagnosis
function. If enabled, the distance to cable errors
can be read out in
12-93 Cable Error Length
. The
parameter resumes to the default setting of Disable
after the diagnostics have finished.
[0] Disabled
[1] Enabled
NOTE
The cable diagnostics function is only issued on ports
where there is no link (see
12-10 Link Status
,
Link Status
)
12-91 Auto Cross Over
Option:
Function:
[0]
Disabled
Disables the auto cross-over function.
[1]
Enabled
Enables the auto cross-over function.
12-93 Cable Error Length
Range:
Function:
0
*
[0 -
65535 ]
If Cable Diagnostics is enabled in
12-90 Cable
Diagnostic
, the built-in switch is possible via
Time Domain Reflectometry (TDR). This
measurement technique detects common
cabling problems such as open circuits, short
circuits, and impedance mismatches or breaks in
transmission cables. The distance from the
option to the error is displayed in meters with
an accuracy of
±
2 m. The value 0 means that no
errors detected.
Parameters
MCA 123 POWERLINK Operating Instructions
MG92C102 - VLT
®
is a registered Danfoss trademark
39