Program the frequency converter as shown in
Table 8.2
.
Parameter
Setting
4-10 Motor Speed Direction
[2] Both directions
5-10 Terminal 18 Digital Input
[0] No operation
5-11 Terminal 19 Digital Input
[10] Reversing
5-40 Function Relay
[36/37] Control word bit 11/12
8-03 Control Word Timeout Time
1 s
8-04 Control Word Timeout Function
[2] Stop
8-10 Control Word Profile
[0] FC Profile
8-50 Coasting Select
[1] Bus
8-51 Quick Stop Select
[1] Bus
8-52 DC Brake Select
[1] Bus
8-53 Start Select
[1] Bus
8-54 Reversing Select
[2] Logic AND
8-55 Set-up Select
[1] Bus
8-56 Preset Reference Select
[1] Bus
Table 8.2 Programming of Frequency Converter
Application Examples
MCA 123 POWERLINK Operating Instructions
MG92C102 - VLT
®
is a registered Danfoss trademark
43
8
8