8-55 Set-up Select
Option:
Function:
[2] Logic AND Activates the set-up selection via the fieldbus/
serial communication port, AND additionally via
one of the digital inputs.
[3] Logic OR
Activate the set-up selection via the fieldbus/
serial communication port OR via one of the
digital inputs.
8-90 Bus Jog 1 Speed
Range:
Function:
100 RPM
*
[ 0 - par. 4-13
RPM]
Enter the jog speed. Activate this
fixed jog speed via the serial port
or fieldbus option.
8-91 Bus Jog 2 Speed
Range:
Function:
200 RPM
*
[ 0 - par. 4-13
RPM]
Enter the jog speed. Activate this
fixed jog speed via the serial port
or fieldbus option.
7.2 Parameter Group 12-** Ethernet
7.2.1 12-0* IP Settings
12-00 IP Address Assignment
Option:
Function:
Selects the IP Address assignment method.
[0]
MANUAL IP-address can be set in
12-01 IP Address
IP
Address.
[1]
DHCP
IP-address is assigned via DHCP server.
[2]
BOOTP
IP-address is assigned via BOOTP server.
[10] DCP
DCP Assigned via the DCP protocol. [20] *From
Node ID address is set from
12-60 Node ID
.
12-01 IP Address
Range:
Function:
0
*
[0 -
2147483647 ]
Configure the IP address of the option.
Read-only if
12-00 IP Address Assignment
set to DHCP or BOOTP. In POWERLINK
the IP address follows the
12-60 Node ID
last byte and the first part is fixed to
192.168.100 (Node ID).
12-02 Subnet Mask
Range:
Function:
0
*
[0 - 4244635647 ] Configure the IP subnet mask of the
option. Read-only if
12-00 IP Address
Assignment
set to DHCP or BOOTP. In
POWERLINK it is fixed to 255.255.255.0.
12-03 Default Gateway
Range:
Function:
0
*
[0 -
2147483647 ]
Configure the IP default gateway of the
option. Read-only if
12-00 IP Address
Assignment
set to DHCP or BOOTP. In a
non-routed network this address is set
to the IP address of the IO Device
12-08 Host Name
Range:
Function:
0
*
[0 -
2147483647 ]
Logical (given) name of option. The
display of the frequency converter only
shows the first 19 characters, but the
remaining characters are stored in the
frequency converter. The frequency
converter can accept longer text than 19
characters, but it is recommended to limit
the length to 19 characters.
12-09 Physical Address
Range:
Function:
0
*
[0 - 0 ] Read only. Displays the Physical (MAC) address of
the option.
7.2.2 12-1* Ethernet Link Parameters
12-1* Ethernet Link parameters
Option:
Function:
Applies for whole parameter group.
[0] Port 1 Index [0] goes for Port 1. For EtherCAT it goes for In
Port.
[1] Port 2 Index [1] goes for Port 2. For EtherCAT it goes for out
Port.
12-10 Link Status
Option:
Function:
Read only. Displays the link status of the Ethernet
ports.
[0] No Link
[1] Link
12-11 Link Duration
Range:
Function:
Size related
*
[ 0 - 0 ] Read only. Displays the duration of the
present link on each port in dd:hh:mm:ss.
12-12 Auto Negotiation
Option: Function:
Configures Auto Negotiation of Ethernet link
parameters, for each port: ON or OFF.
[0] Off
Link Speed
and
Link Duplex
can be configured in
12-13 Link Speed
and
12-14 Link Duplex
.
Parameters
MCA 123 POWERLINK Operating Instructions
MG92C102 - VLT
®
is a registered Danfoss trademark
37