19. Position the guide pin in the adapter
flange.
18. Assemble the new O-ring on the correct
sealing plate.
It is important to lubricate to ensure the
O-ring does not drop out.
20. Position the sealing plate over the guide
pin.
21. Carefully position the adapter flange
assembly into the two guide pin holes.
22. Mount two bolts in the adapter flange.
23. Mount all bolts in the adapter flange.
Tighten the bolts to a torque of 60±6 Nm.