Application Guide | iC2-Micro Frequency Converters
Table 47: Query
(continued)
Field name
Example (hex)
Write data HI (Register 4: 1049)
00
Write data LO (Register 4: 1049)
00
Write data HI (Register 4: 1050)
02
Write data LO (Register 4: 1050)
E2
Error check (CRC)
–
Response
The normal response returns the follower address, function code, starting address, and quantity of registers preset.
Table 48: Response
Field name
Example (hex)
Follower address
01
Function
10
Starting address HI
04
Starting address LO
19
Number of registers HI
00
Number of registers LO
02
Error check (CRC)
–
6.1.7.6.6
Force/Write Multiple Coils (0F hex)
Description
This function forces each coil in a sequence of coils to either on or off. When broadcasting, the function forces the same coil references in
all attached followers.
Query
The query telegram specifies the coils 17–32 (speed setpoint) to be forced.
NOTICE
Coil addresses start at 0, that is, coil 17 is addressed as 16.
Table 49: Query
Field name
Example (hex)
Follower address
01 (drive address)
Function
0F (write multiple coils)
Coil address HI
00
Coil address LO
10 (coil address 17)
Danfoss A/S © 2024.03 AB413939445838en-000301 / 130R1254 |
95
Summary of Contents for iC2
Page 1: ...iC2 Micro Frequency Converters Application Guide drives danfoss com...
Page 2: ......
Page 291: ......