Selection number
Selection name
Selection description
0
No Operation
Default for all digital outputs.
1
Control Ready
The control card is ready.
2
Drive Ready
The frequency converter is ready for operation and applies a
supply signal on the control board.
3
Drive Ready / Remote Mode
The frequency converter is ready for operation and is in Remote
mode.
4
Stand-by / No Warning
Ready for operation. No start or stop command is given (start/
disable). No warnings are active.
5
Running
The motor is running and shaft torque is present.
6
Running / No Warning
The motor is running and there are no warnings.
7
Run in Range / No Warning
The motor is running within the programmed current and speed
ranges set in
P 4.6.4 Warning Current Low
to
P 4.6.3 Warning
Current High
. There are no warnings.
8
Run on Ref. / No Warning
The motor runs at reference speed. No warnings.
9
Fault
A fault activates the output.
10
Fault or Warning
A fault or a warning activates the output.
11
At Torque Limit
The torque limit set in
P 5.10.1 Motor Torque Limit
or
P 5.10.2
Regenerative Torque Limit
has been exceeded.
12
Out of Current Range
The motor current is outside the range set in
P 2.7.1 Output
Current Limit %
.
13
Below Current, Low
The motor current is lower than set in
P 4.6.4 Warning Current
Low
.
14
Above Current, High
The motor current is higher than set in
P 4.6.3 Warning Current
High
.
15
Out of Frequency Range
Output frequency is outside the frequency range.
16
Below Frequency, Low
The output speed is lower than the setting in
P 4.6.2 Warning
Freq. Low
.
17
Above Frequency, High
The output speed is higher than the setting in
P 4.6.1 Warning
Freq. High
.
18
Out of Feedback Range
The feedback is outside the range set in
P 5.2.4 Warning
Feedback Low
and
P 5.2.3 Warning Feedback High
.
19
Below Feedback, Low
The feedback is below the limit set in
P 5.2.4 Warning Feedback
Low
.
20
Above Feedback, High
The feedback is above the limit set in
P 5.2.3 Warning Feedback
High
.
21
Thermal Warning
The thermal warning turns on when the temperature exceeds
the limit in the motor, the frequency converter, the brake resistor,
or the thermistor.