Application Guide | iC2-Micro Frequency Converters
Selection number
Selection name
0
200-240V/50Hz/IT-grid
1
200-240V/50Hz/Delta
2
200-240V/50Hz
5
100-110V/50Hz/IT-grid
6
100-110V/50Hz/Delta
7
100-110V/50Hz
10
380-440V/50Hz/IT-grid
11
380-440V/50Hz/Delta
12
380-440V/50Hz
20
440-480V/50Hz/IT-grid
21
440-480V/50Hz/Delta
22
440-480V/50Hz
100
200-240V/60Hz/IT-grid
101
200-240V/60Hz/Delta
102
200-240V/60Hz
105
100-110V/60Hz/IT-grid
106
100-110V/60Hz/Delta
107
100-110V/60Hz
110
380-440V/60Hz/IT-grid
111
380-440V/60Hz/Delta
112
380-440V/60Hz
120
440-480V/60Hz/IT-grid
121
440-480V/60Hz/Delta
122
440-480V/60Hz
7.2.2
Grid Protection (Menu Index 1.3)
P 1.3.1 Mains Imbalance Action
Select an action of frequency converter on detecting a severe mains imbalance. Operation during severe mains imbalance reduces the
lifetime of the frequency converter. When selecting
[4] Fast Trip
or
[5] Fast Warning
,
P 1.2.1 Regional settings
must match the frequency
of actual grid to avoid false faults.
Conditions are considered severe if the motor is operated continuously near nominal load (for example, a pump or fan running near full
speed).
Default value:
0 [Trip]
Parameter type:
Selection
Danfoss A/S © 2024.03 AB413939445838en-000301 / 130R1254 |
107