Table 36: Drive Control Word (FC Profile)
(continued)
Coil
0
1
04
Coast stop
No coast stop
05
Quick stop
No quick stop
06
Freeze frequency
No freeze frequency
07
Ramp stop
Start
08
No reset
Reset
09
No jog
Jog
10
Ramp 1
Ramp 2
11
Data not valid
Data valid
12
Relay 1 off
Relay 1 on
13
Reserved
14
Set up LSB
15
Reserved
16
No reversing
Reversing
Drive Status Word (FC Profile)
Table 37: Drive Status Word (FC Profile)
Coil
0
1
33
Control not ready
Control ready
34
Drive not ready
Drive ready
35
Coast stop
Safety closed
36
No alarm
Alarm
37
Not used
Not used
38
Not used
Not used
39
Not used
Not used
40
No warning
Warning
41
Not at reference
At reference
42
Local mode
Remote mode
43
Out of frequency range
In frequency range
44
Stopped
Running
45
Not used
Not used
46
No voltage warning
Voltage warning
88
| Danfoss A/S © 2024.03 AB413939445838en-000301 / 130R1254
Application Guide | iC2-Micro Frequency Converters