Selection number
Selection name
Selection description
2
Logic AND
The fieldbus/serial communication port and a digital input
trigger the preset reference selection.
3
Logic OR
The fieldbus/serial communication port or a digital input triggers
the preset reference selection.
7.6.4.3
Reference (Menu Index 5.5.3)
P 5.5.3.1 Reference Range
Use this parameter to select the range of the reference signal and the feedback signal.
Default value:
0 [Min–Max]
Parameter type:
Selection
Parameter
number:
300
Unit:
–
Data type:
enum
Access type:
Read/Write
The following are the selections for the parameter.
Selection number
Selection name
Selection description
0
Min–Max
Select the range of the reference signal and the feedback signal.
Signal values can be positive only, or positive and negative.
1
-Max–Max
For both positive and negative values (both directions), relative
to
P 5.8.1 Rotation Direction
.
P 5.5.3.2 Reference/Feedback Unit
Use this parameter to select the unit to be used in Process PID Control references and feedback.
Default value:
3 [Hz]
Parameter type:
Selection
Parameter
number:
301
Unit:
–
Data type:
enum
Access type:
Read/Write
The following are the selections for the parameter.
Selection number
Selection name
0
None
1
%
2
RPM
3
Hz
4
Nm
5
PPM
156
| Danfoss A/S © 2024.03 AB413939445838en-000301 / 130R1254
Application Guide | iC2-Micro Frequency Converters