Application Guide | iC2-Micro Frequency Converters
Parameter
number:
2262
Unit:
s
Data type:
uint16
Access type:
Read/Write
P 5.2.16 Watchdog Response
Use this parameter to select the timeout function. The timeout function activates when the control word fails to be updated within the
time period specified in
P 5.2.17 Watchdog Delay
.
Default value:
0 [Off]
Parameter type:
Selection
Parameter
number:
804
Unit:
–
Data type:
enum
Access type:
Read/Write
The following are the selections for the parameter.
Selection number
Selection name
0
Off
1
Freeze Output
2
Stop
3
Jogging
4
Max. Speed
5
Stop and Trip
6
Qstop and Trip
7
Select Setup 1
8
Select Setup 2
26
Trip
P 5.2.17 Watchdog Delay
Use this parameter to enter the maximum time expected to pass between the reception of 2 consecutive telegrams. If this time is
exceeded, it indicates that the serial communication has stopped, and the function selected in
P 5.2.16 Watchdog Response
is then
carried out.
Default value:
1.0
Parameter type:
Range (0.5–6000.0)
Parameter
number:
803
Unit:
s
Data type:
uint16
Access type:
Read/Write
Danfoss A/S © 2024.03 AB413939445838en-000301 / 130R1254 |
147