VLT
®
AutomationDrive EtherNet/IP
MG.90.J1.02 – VLT is a registered Danfoss trademark
52
Class ID 0x06 Connection Manager
Instance Attributes
Attribute
Access
Name
Data Type
Description
1
Get
Open Requests
UINT
Number of Forward Open requests
received
2
Get
Open Format Rejects
UINT
Number of Forward Open requests
rejected due to bad format
3
Get
Open Resource Rejects
UINT
Number of Forward Open requests
rejected due to lack of resources
4
Get
Open Other Rejects
UINT
Number of Forward Open requests
rejected due to other reasons
5
Get
Close Requests
UINT
Number of Forward Close requests
received
6
Get
Close Format Requests
UINT
Number of Forward Close requests
rejected due to bad format
7
Get
Close Other Requests
UINT
Number of Forward Close requests
rejected due to other reasons
8
Get
Connection Timeouts
UINT
Number of connection timeouts
Connection Entry List
Struct of:
NumConnEntries
INT
Number of connection entries
9 Get
ConnOpenBits ARRAY
of
BOOL
List of connection data
Class ID 0x28 Motor Data Object
Instance Attributes
Attribute Access
Name
Data Type Parameter
Description
1
Get
Number of Attributes
supported
USINT -
7
2
Get
List of attributes
supported
Array of
USINT
- 3,6,7,8,9,12,15
3
Get/Set Motor Type
USINT
1-10
3: PM sync. motor (FC 302 only)
7: Squirrel cage induction motor
6
Get/Set Rated Current
UINT
1-24
Unit: 100 mA
7
Get/Set Rated Voltage
UINT
1-22
Unit: Volt
8
Get/Set Rated Power
UDINT
1-20
Unit: Watt
9
Get/Set Rated Frequency
UINT
1-23
Unit: Hertz
12
Get/Set Pole Count
UINT
1-39
Number of poles in motor
15
Get/Set Base Speed
UINT
1-25
Unit: RPM
N.B.
Class ID 0x28 is only available if ODVA profile is selected in par. 8-10.