VLT
®
AutomationDrive EtherNet/IP
MG.90.J1.02 – VLT is a registered Danfoss trademark
9
LED Behaviour
The option has 3 bi-coloured LED’s according to ODVA specifications:
LED label
Description
MS Module
Status
NS1
Network Status Ethernet Port 1
NS2
Network Status Ethernet Port 2
The option LED’s operates according to ODVA specifications.
MS: Module Status
State
LED
Description
No power
Off
The device is un-powered
Device
operational
Green:
█████████████
Solid green
The device is operational
Standby
Green: ██████
Flashing green
The device needs commissioning
Minor fault
Red:
███████
Flashing red
The device has detected a recoverable
fault
Major fault
Red: ██████████████
Solid red
The device has detected a un-recoverable
fault
Self test
Red:
███████
Green: ██████
Flashing red/green The EIP option is in self-test mode.
NS1 + NS2: Network status (one per port)
State
LED
Description
No IP-address
(no power)
Off
The device does not have a valid IP-
address (or is un-powered)
No connections Green:
██████
Flashing green
There are no established any CIP
connections to the device
Connected
Green:
████████████
Steady green
There is established (at least) one CIP
connection to the device
Connection
time-out
Red:
██████
Flashing red
One or more CIP connections has timed-
out
Duplicate IP
Red:
█████████████
Steady red
The IP-address assigned to the device is
already in use
Self test
Red:
███████
Green: ██████
Flashing red/green The EIP option is in self-test mode.
During normal operation the MS and at least one NS LED will show a constant green light.