VLT
®
AutomationDrive EtherNet/IP
- P a r a m e t e r s –
MG.90.J1.02 – VLT is a registered Danfoss trademark
34
Logic
Rule
5
[75]
SL digital out A
[80]
SL digital out B
[81]
SL digital out C
[82]
SL digital out D
[83]
SL digital out E
[84]
SL digital out F
[85]
Function:
Enables configuration of bit 12 to 15 in the
Status Word. Profile Default corresponds to the
profile default setting in par. 8-10
Control Word
Profile.
(8-50) Coasting Select
Option:
Digital
input
[0]
Bus
[1]
Logic
AND
[2]
*Logic
OR
[3]
Function:
Select control of the coasting function via the
terminals (digital input) and/or via the fieldbus.
Select
Bus
[1], to activate the Start command
via the serial communication port or fieldbus
option.
Select
Logic AND
[2]
to activate the Start
command via the fieldbus/serial
communication port, AND additionally via one
of the digital inputs.
Select
Logic OR [3]
to activate the Start
command via the fieldbus/serial
communication port OR via one of the digital
inputs.
N.B.
This parameter is active only when
par. 8-01
Control site
is set to [0]
Digital
and control word.
(8-51) Quick Stop Select
Option:
Digital
input
[0]
Bus
[1]
Logic
AND
[2]
*Logic
OR
[3]
Function:
Select control of the Quick Stop function via
the terminals (digital input) and/or via the
fieldbus.
N.B.
This parameter is active only when
par. 8-01
Control site
is set to [0]
Digital
and control word.
(8-52) DC Brake Select
Option:
Digital
input
[0]
Bus
[1]
Logic
AND
[2]
*Logic
OR
[3]
Function:
Select control of the DC brake via the terminals
(digital input) and/or via the fieldbus.
N.B.
This parameter is active only when
par. 8-01
Control site
is set to [0]
Digital
and control word.
(8-53) Start Select
Option:
Digital
input
[0]
Bus
[1]
Logic
AND
[2]
*Logic
OR
[3]
Function:
Select control of the frequency converter start
function via the terminals (digital input) and/or
via the fieldbus.
N.B.
This parameter is active only when
par. 8-01
Control site
is set to [0]
Digital
and control word.
(8-54) Reversing Select
Option:
Digital
input
[0]
Bus
[1]
Logic
AND
[2]
*Logic
OR
[3]
Function:
Select control of the frequency converter
reverse function via the terminals (digital
input) and/or via the fieldbus.
N.B.
This parameter is active only when
par. 8-01
Control site
is set to [0]
Digital
and control word.