(12-20) Control Instance
Option:
*None, 20, 21, 100, 101, 103
Function:
Read only.
Displays the originator-to-target connection
point. If no CIP connection is present “None” is
displayed.
(12-21) Process Data Config Write
Option:
[0 - 9] PCD write 0 - 9
Function:
Configuration of writeable process data.
(12-22) Process Data Config Read
Option:
[0 - 9] PCD read 0 - 9
Function:
Configuration of readable process data.
N.B.:
For configuration of 2-word (32-
bit) parameter read/write, use 2
consecutive arrays in par. 12-21 and 12-
22.
(12-28) Store Data Values
Option:
*Off
[0]
Store
All
set-up’s [1]
Function:
This parameter activates a function that stores
all parameter values in the non-volatile
memory (EEPROM) thus retaining parameter
values at power-down.
- Off: The store function is inactive.
- Store All set-up’s: All parameter value
will be stored in the non-volatile memory,
in all four setups.
The parameter returns to “Off”.
(12-21) Store Always
Option:
*Off
[0]
On
[1]
Function:
Activates function that will always store
received parameter data in non-volatile
memory (EEPROM).