VLT
®
AutomationDrive EtherNet/IP
- P a r a m e t e r s –
MG.90.J1.02 – VLT is a registered Danfoss trademark
33
- Freeze output [1]: Freeze output frequency
until communication resumes.
- Stop [2]: Stop with auto restart when
communication resumes.
- Jogging [3]: Run the motor at JOG frequency
until communication resumes.
- Max. freq.. [4]: Run the motor at maximum
frequency until communication resumes.
- Stop and trip[5]: Stop the motor, then reset
the frequency converter in order to restart: via
the fieldbus, via the reset button on the LCP or
via a digital input.
- Select set-up 1-4 [7] - [10]: This option
changes the set-up upon reestablishment of
communication following a control word time-
out. If communication resumes causing the
time-out situation to disappear, par. 8-05 End-
of-time-out Function defines whether to
resume the set-up used before the time-out or
to retain the set-up endorsed by the time-out
function. Note the following configuration
required in order to change the set-up after a
time-out: Set Par. 0-10 Active set-up to Multi
set-up [9], and select the relevant link in par.
0-12 This Set-up Linked To.
(8-05) End-of-timeout Function
Option:
*Hold
set-up
[0]
Resume
set-up [1]
Function:
Select the action after receiving valid CTW
following a time-out. This parameter is active
only when par. 8-04 is set to Set-up 1-4.
Hold: The frequency converter retains the set-
up selected in par. 8-04 and displays a
warning, until par. 8-06 toggles. Then the
frequency converter resumes its original set-
up.
Resume: The frequency converter resumes the
set-up active prior to the time-out.
(8-06) Reset Control Word Timeout
Option:
*Do not reset
[0]
Do
reset
[1]
Function:
Select Do reset [1] to return the frequency
converter to the original set-up following a
control word time-out. When the value is set to
Do reset [1], the frequency converter performs
the reset and then immediately reverts to the
Do not reset [0] setting.
Select Do not reset [0] to retain the set-up
specified in par. 8-04 Select setup 1-4
following a control word time-out.
This parameter is active only when Hold set-up
[0] has been selected in par. 8-05 End- of-
Time-out Function.
(8-07) Diagnosis Trigger
Option:
*Disable
[0]
Trigger on alarms
[1]
Trigger on alarms/warn.
[2]
Function:
This parameter has no function for EtherNet/IP.
(8-10) Control Word Profile
Option:
*FC
profile
[0]
ODVA
[5]
Function:
Select the interpretation of the control and
status words corresponding to the installed
fieldbus. Only the selections valid for the
fieldbus installed in slot A will be visible in the
LCP display.
(8-13) Configurable Status Word
Option:
No
function
[0]
* Profile Default
[1]
Alarm
68
Only
[2]
Trip excl Alarm 68
[3]
T18
DI
status
[10]
T19
DI
status
[11]
T27
DI
status
[12]
T29
DI
status
[13]
T32
DI
status
[14]
T33
DI
status
[15]
T37
DI
status
[16]
Thermal
warning [21]
Brake fault (IGBT)
[30]
Out of ref range
[40]
Comparator
0
[60]
Comparator
1
[61]
Comparator
2
[62]
Comparator
3
[63]
Comparator
4
[64]
Comparator
5
[65]
Logic Rule 0
[70]
Logic Rule 1
[71]
Logic Rule 2
[72]
Logic
Rule
3
[73]
Logic
Rule
4
[74]