Supported CIP Objects
As in all implementations of CIP, EtherNet/IP shares the common Object Model.
Objects are a common method to describe the specific application implemented in a device.
Data is structured in Classes, Instances and Attributes:
A
class
is a group of objects with the same structure. These groups of objects within a class
are called
instances
. Every instance provides the same data elements called
attributes
.
Each class provides services to access data or to change the state of an object.
Class ID 0x01 Identity Object
Instance Attributes
Attribute
Access
Name
Data type
Description
1
Get
Vendor
UINT
(97) Danfoss Drives vendor code
2
Get
Device Type
UINT
(2) AC Drive
3
Get
Product Code
UINT
Value of par. 12-34
4
Get
Revision
Struct
Value of par. 12-33
5
Get
Status
WORD
EIP status word (par. 12-30)
6
Get
Serial Number
UDINT
Serial number
7
Get
Product Name
String
Value of par. 15-40 (e.g. “FC-302”)
8
Get
State
UINT
0 = Non-existent
1 = Device Self Testing
2 = Standby
3 = Operational
4 = Major Recoverable Fault
5 = Major Unrecoverable Fault
6-254 = Reserved
255 = Default for Get Attribute All
9 Get
Conf.
consistency
value
UINT
Class ID 0x04 Assembly Objects
Instance Attributes
Instance
Access
Name
Size
Description
20
Set
ODVA basic speed control
Output
2 Words
21
Set
ODVA extended speed
control Output
2 Words
70
Get
ODVA basic speed control
Input
2 Words
71
Get
ODVA extended speed
control Input
2 Words
100
Set
Danfoss Basic Control
Output
2 Words
101
Set
Danfoss Extended Control
Output
4 Words
103
Set
Danfoss Extended Control
Output
10 Words
150
Get
Danfoss Basic Control
Input
2 Words
151
Get
Danfoss Extended Control
Input
4 Words
153
Get
Danfoss Extended Control
Input
10 Words