164
|
Dali Matrix PS System Installation and Commissioning Guide
Dali Wireless Proprietary and Confidential | DW-MAN-036 Rev 06
14.3
Reviewing and Resolving Alarms
Once the reference clock is configured and optical ports are active, review any alarms
displayed in the system tree. For Major and Critical alarms, address the cause and
continue commissioning only when the alarm is cleared. If the alarms are Minor, you can
continue commissioning without affecting service. However, be aware that alarms can
escalate to Critical if left unaddressed.
The following table describes the alarm state colors.
Alarm Color
(system tree)
Alarm Icon
(title bar)
Alarm State
Description
Red vibrating
Critical
Any service-affecting failure. A site visit may be
required. On the physical device, the LED is red
flashing.
Red
Major
A failure condition that is not service-affecting but must
be addressed. Major alarms can escalate to critical if
not resolved.
Orange
Minor
Warnings for planned outages or minor failures that
don’t prevent continued operation. For example, Low
Power or RF path not active.
However, some optical failure alarms for daisy-chained
hosts display as Minor but should be addressed as
Critical. See
Optical Link Failure Alarms on Daisy-
Green
No alarm
No alarm.
14.3.1
Displaying the Alarm Summary
For information about the current alarms for each unit, display the Alarm Summary by
clicking the alarm icon in the blue bar of a host or remote. Click each alarm link to display a
description and corrective action.