![background image](http://html1.mh-extra.com/html/daikin/super-multi-nx-ffq25b8v1b/super-multi-nx-ffq25b8v1b_service-manual_4061781117.webp)
SiBE121021_C
Function of Indoor Unit (SA Models)
Function and Control
105
2.1.3 When the Float Switch is Tripped During Heating Operation:
During heating operation, if the float switch is not reset even after the 5 minutes operation, 5
seconds stop, 5 minutes operation cycle ends, operation continues until the switch is reset.
2.1.4 When the Float Switch is Tripped and “
AF
” is Displayed on the
Remote Controller:
*4. (Malfunction residual):
If the float switch is tripped 5 times in succession, a drain malfunction is determined to have
occurred. “
AF
” is then displayed as operation continues.
*5. (Malfunction residual):
The remote controller displays "
A3
" and the air conditioner comes to an abnormal stop if the float
switch is OFF for more than 5 minutes in the case of *4.
The remote controller displays "
A3
" and the indoor unit stops.
Thermostat
(running)
Humidifier
Float switch
Drain pump
ON
OFF
ON
OFF
ON
OFF
ON
OFF
Reset
5 min.
5 sec.
5 min.
(R12935)
The indoor unit enters malfunction
treatment if the float switch is not
reset within 5 minutes.
The remote controller displays "
A3
"
and the indoor unit stops.
"
AF
" display (running)
Remote
controller display
Float switch
Drain pump
*1: 5min
1st time 2nd time 3rd time 4th time 5th time
*1
*1
*1
*1
*1
*1
*4
*5
*1
5 sec.
ON
ON
ON
OFF
OFF
OFF
(R12936)