Troubleshooting for RA Indoor Unit - F(C)TXG, FTXS, ATXS, FVXS, FLK(X)S, FDK(X)S Series
SiBE121021_C
312
Service Diagnosis
Troubleshooting
Check No.02
Refer to P.363
Check No.02
Check the output of the
fan motor connector
YES
YES
NO
YES
YES
NO
NO
NO
Note : The motor may break when the
motor connector is disconnected
while remaining power supply.
Caution
Replace the fan
motor.
Replace the indoor
unit PCB.
Replace the indoor
unit PCB.
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Check No.02
Check the output of the
fan motor connector
(R14404)
NO
YES
YES
NO
YES
NO
Replace the fan
motor.
Replace the indoor
unit PCB.
Replace the indoor
unit PCB.
Replace the fan
motor.
Replace the fan
motor and the
indoor unit PCB.
Turn off the power supply
and rotate the fan by
hand.
Does the fan rotate
smoothly?
Turn the power on and
start operation.
Does the fan
rotate?
Stop the fan motor.
Is the rotation
number
command pulse
generated?
Is the rotation
number
command pulse
generated?
Is the
rotation
command
voltage 1 ~ 5
VDC
generated?
Is the motor
control voltage 15
VDC generated?
Is the motor
power supply
voltage 310 ~ 340
VDC generated?
Turn off the power supply
and disconnect the fan
motor connector, then
turn the power on.