![background image](http://html1.mh-extra.com/html/daikin/super-multi-nx-ffq25b8v1b/super-multi-nx-ffq25b8v1b_service-manual_4061781469.webp)
SiBE121021_C
Field Settings
Trial Operation and Field Settings
457
Wireless Remote
Controller
(Factory Set is
“1”)
1. Hold down the “
” button and the “
” button at the same time for at least
4 seconds to enter the field setting mode. (“SETTING” is indicated on the display).
2. Press the “
” button and select “A” or “b”. Each time the button is pressed, the
display switches between “A” and “b”.
3. Press the “
” button and “
” button to set the address.
Address can be set from 1 ~ 6, but set it to 1 ~ 3 and to same address as the receiver. (The
receiver does not work with address 4 ~ 6.)
4. Press the “
” button to confirm the setting.
5. Hold down the “
” button for at least 1 second to exit the field setting mode and
return to the normal display.
Multiple Settings
A/b
When the indoor is controlled by outside controller (central remote controller, etc.), it sometimes
does not respond to ON/OFF command or temperature setting command from the remote
controller. Check what setting the customer needs and make the multiple setting as shown
below.
Field setting mode
Address
Multiple setting
(R14401)
Remote Controller
Indoor Unit
Multiple Setting
Remote Controller
Display
Controlled by other air
conditioners or devices
Other condition
A: Standard
All items are displayed. ON/OFF command and
temperature setting
command cannot be
accepted. (1 long beep
or 3 short beeps
emitted)
b: Multiple display
Operations set only is
displayed shortly after
execution.
All the commands can be accepted (2 short
beeps)