SiBE121021_C
Outdoor Unit - 50~75 Class
Removal Procedure
379
13
Disconnect the each
connector.
[S90] : Thermistors
(outdoor
temperature,
outdoor heat
exchanger,
discharge pipe)
[S92] : Gas pipe
thermistors
[S93] : Liquid pipe
thermistors
14
Disconnect the
connector for the four
way valve coil [S80].
The cooling only models
have no harness for [S80].
Step
Procedure
Points
[S90]
[S92]
[S93]
[S80]