Specifications
ESIE04-01
1–46
Part 1 – System Outline
3
11
4
5
Symbols:
MCA: Min. Circuit Amps
TOCA: Total Over-current Amps
MFA: Max. Fuse Amps (see note 7)
MSC : Max. current during the starting compressor
RLA : Rated Load Amps
OFM : Outdoor Fan Motor
IFM : Indoor Fan Motor
FLA : Full Load Amps
kW : Fan Motor Rated Output
Notes:
1
RLA is based on the following conditions:
P
Power supply: 50Hz 230V
P
Indoor temp. - cooling: 27°C DB/19.0°C WB
P
Indoor temp. - heating: 20.0°C DB
P
Outdoor temp. - cooling: 35.0°C DB
P
Outdoor temp. - heating: 7.0°C DB/6.0°C WB
2
TOCA means the total value of each OC set.
3
Voltage range
Units are suitable for use on electrical systems where voltage
supplied to unit terminals is not below or above listed range limits.
4
Maximum allowable voltage variation between phases is 2%.
5
MCA represents maximum input current.
MFA represents capacity which may accept MCA. (Next lower standard fuse rating, minimum 15A)
6
Select wire size based on the larger value of MCA or TOCA.
7
MFA is used to select the circuit breaker and the ground fault circuit interruptor. (earth leakage circuit breaker)
FCQ125B7V3B
RZQ125B7V3B
50-230
Max.50Hz-253V
Min.50Hz-207V
25.0
25.0
30
23.4
23.4
0.07+0.07
0.3+0.3
0.090
1.0
FCQ60B7V1x2
RZQ125B7V3B
50-230
25.2
25.2
30
23.4
23.4
0.07+0.07
0.3+0.3
0.045x2
0.6x2
FCQ50B7V1x3
RZQ125B7V3B
50-230
25.8
25.8
30
23.4
23.4
0.07+0.07
0.3+0.3
0.045x3
0.6x3
FCQ35B7V1x4
RZQ125B7V3B
50-230
26.4
26.4
30
23.4
23.4
0.07+0.07
0.3+0.3
0.045x4
0.6x4
FFQ60BV1Bx2
RZQ125B7V3B
50-230
25.4
25.4
30
23.4
23.4
0.07+0.07
0.3+0.3
0.055x2
0.7x2
FFQ50BV1Bx3
RZQ125B7V3B
50-230
26.1
26.1
30
23.4
23.4
0.07+0.07
0.3+0.3
0.055x3
0.7x3
FFQ35BV1Bx4
RZQ125B7V3B
50-230
26.4
26.4
30
23.4
23.4
0.07+0.07
0.3+0.3
0.055x4
0.6x4
FBQ125B7V3B
RZQ125B7V3B
50-230
25.4
25.4
30
23.4
23.4
0.07+0.07
0.3+0.3
0.225
1.4
FBQ60B7V1x2
RZQ125B7V3B
50-230
25.8
25.8
30
23.4
23.4
0.07+0.07
0.3+0.3
0.125x2
0.9x2
FBQ50B7V1x3
RZQ125B7V3B
50-230
26.1
26.1
30
23.4
23.4
0.07+0.07
0.3+0.3
0.085x3
0.7x3
FBQ35B7V1x4
RZQ125B7V3B
50-230
26.0
26.0
30
23.4
23.4
0.07+0.07
0.3+0.3
0.065x4
0.5x4
FHQ125BUV1B
RZQ125B7V3B
50-230
24.7
24.7
30
23.4
23.4
0.07+0.07
0.3+0.3
0.130
0.7
FHQ60BUV1Bx2
RZQ125B7V3B
50-230
25.2
25.2
30
23.4
23.4
0.07+0.07
0.3+0.3
0.062x2
0.6x2
FHQ50BUV1Bx3
RZQ125B7V3B
50-230
25.8
25.8
30
23.4
23.4
0.07+0.07
0.3+0.3
0.062x3
0.6x3
FHQ35BUV1Bx4
RZQ125B7V3B
50-230
26.4
26.4
30
23.4
23.4
0.07+0.07
0.3+0.3
0.062x4
0.6x4
FUQ125BUV1B
RZQ125B7V3B
50-230
25.1
25.1
30
23.4
23.4
0.07+0.07
0.3+0.3
0.090
1.1
FDQ125B7V3B
RZQ125B7V3B
50-230
28.2
28.2
30
23.4
23.4
0.07+0.07
0.3+0.3
0.500
4.2
Unit combination
Power supply
Compressor
OFM
IFM
RZQ - Final.book Page 46 Wednesday, September 8, 2004 8:40 AM
Summary of Contents for RZQ71~125B7V3B
Page 1: ...Service Manual ESIE04 01 RZQ71 125B7V3B Sky Air Inverter R 410A B series ...
Page 2: ......
Page 24: ...ESIE04 01 1 2 Part 1 System Outline 3 1 1 5 ...
Page 32: ...General Outline Outdoor Units ESIE04 01 1 10 Part 1 System Outline 3 1 1 4 5 ...
Page 64: ...General Outline Indoor Units ESIE04 01 1 42 Part 1 System Outline 3 1 1 4 5 ...
Page 76: ...Specifications ESIE04 01 1 54 Part 1 System Outline 3 1 1 4 5 ...
Page 92: ...Functional Diagrams ESIE04 01 1 70 Part 1 System Outline 3 1 1 4 5 ...
Page 94: ...ESIE04 01 1 72 Part 1 System Outline ...
Page 122: ...Wiring Diagrams ESIE04 01 1 100 Part 1 System Outline 3 1 1 4 5 ...
Page 140: ...ESIE04 01 2 2 Part 2 Functional Description 3 1 2 5 ...
Page 162: ...General Functionality ESIE04 01 2 24 Part 2 Functional Description 3 1 2 4 5 ...
Page 200: ...Outdoor Unit Functional Concept ESIE04 01 2 62 Part 2 Functional Description 3 1 2 4 5 ...
Page 202: ...ESIE04 01 3 2 Part 3 Troubleshooting 3 1 3 5 ...
Page 288: ...Error Codes Outdoor Units ESIE04 01 3 88 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 312: ...Additional Checks for Troubleshooting ESIE04 01 3 112 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 314: ...ESIE04 01 4 2 Part 4 Commissioning and Test Run 3 1 4 5 ...
Page 356: ...ESIE04 01 5 2 Part 5 Disassembly and Maintenance 3 1 5 ...
Page 484: ...ESIE04 01 viii Index 3 1 4 5 ...