ESIE04-01
Troubleshooting
Part 3 – Troubleshooting
3–35
3
3
4
5
1
1.9.2
Outdoor malfunctions
Notes:
1
Possibility of open phase in power supply.
2
In RZQ model, L8 is not displayed on remote controller. Please see 3–74 for more detail.
Outdoor Unit
Malfunction
Remote
Controller
Display
Location of Malfunction
Contents of Malfunction
Details of
Malfunction
(Reference
Page)
Other
than PC
Board
PC Board
Outdoor
Unit
Indoor
Unit
Remote
Controller
E0
—
—
Activation of protection device
Note 1.
3–54
E1
—
—
Outdoor unit P.C board malfunc-
tion
3–55
E3
—
—
—
Abnormality of high pressure
(HPS)
3–56
E4
—
—
Abnormality of low pressure
(outdoor)
3–58
E5
—
—
Compressor motor lock malfunc-
tion
3–60
E7
Malfunction of outdoor unit fan
motor
3–62
E9
—
—
Malfunction of Electronic expan-
sion valve
3–63
F3
—
—
Discharge pipe temperature
malfunction
3–65
H3
—
—
Faulty high pressure switch
(HPS)
3–67
H7
—
—
Malfunction of outdoor fan signal 3–68
H9
—
—
Malfunction of outdoor air
temperature sensor system
3–69
J3
—
—
Malfunction of discharge pipe
temperature sensor system
3–69
J5
—
—
Suction pipe thermistor
malfunction
3–69
J6
—
—
Malfunction of heat exchanger
temperature sensor system
3–69
JC
—
—
Suction pipe pressure sensor
malfunction
3–70
L4
—
—
High temperature of radiation fin 3–71
L5
—
—
Overcurrent of DC output
(instantaneous)
3–72
L8
Note 2
—
—
Electronic thermal switch
(time lag)
3–74
L9
—
—
Stall prevention (time lag)
3–76
LC
—
—
Malfunction of transmission sys-
tem (between control PCB and
inverter PCB)
3–78
P1
—
—
Open phase or voltage unbal-
ance
3–80
P4
—
—
Malfunction of radiator fin tem-
perature thermistor
3–82
PJ
—
—
Error in capacity setting
3–84
U0
—
—
—
Gas shortage
3–85
U2
—
—
Abnormal power supply voltage
3–86
RZQ - Final.book Page 35 Wednesday, September 8, 2004 8:40 AM
Summary of Contents for RZQ71~125B7V3B
Page 1: ...Service Manual ESIE04 01 RZQ71 125B7V3B Sky Air Inverter R 410A B series ...
Page 2: ......
Page 24: ...ESIE04 01 1 2 Part 1 System Outline 3 1 1 5 ...
Page 32: ...General Outline Outdoor Units ESIE04 01 1 10 Part 1 System Outline 3 1 1 4 5 ...
Page 64: ...General Outline Indoor Units ESIE04 01 1 42 Part 1 System Outline 3 1 1 4 5 ...
Page 76: ...Specifications ESIE04 01 1 54 Part 1 System Outline 3 1 1 4 5 ...
Page 92: ...Functional Diagrams ESIE04 01 1 70 Part 1 System Outline 3 1 1 4 5 ...
Page 94: ...ESIE04 01 1 72 Part 1 System Outline ...
Page 122: ...Wiring Diagrams ESIE04 01 1 100 Part 1 System Outline 3 1 1 4 5 ...
Page 140: ...ESIE04 01 2 2 Part 2 Functional Description 3 1 2 5 ...
Page 162: ...General Functionality ESIE04 01 2 24 Part 2 Functional Description 3 1 2 4 5 ...
Page 200: ...Outdoor Unit Functional Concept ESIE04 01 2 62 Part 2 Functional Description 3 1 2 4 5 ...
Page 202: ...ESIE04 01 3 2 Part 3 Troubleshooting 3 1 3 5 ...
Page 288: ...Error Codes Outdoor Units ESIE04 01 3 88 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 312: ...Additional Checks for Troubleshooting ESIE04 01 3 112 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 314: ...ESIE04 01 4 2 Part 4 Commissioning and Test Run 3 1 4 5 ...
Page 356: ...ESIE04 01 5 2 Part 5 Disassembly and Maintenance 3 1 5 ...
Page 484: ...ESIE04 01 viii Index 3 1 4 5 ...