Error Codes: Outdoor Units
ESIE04-01
3–62
Part 3 – Troubleshooting
3
1
3
4
5
3.7
Malfunction of Outdoor Unit Fan Motor (
E7
)
Remote Controller
Display
E7
Method of
Malfunction
Detection
Abnormality of fan motor system is detected according to the fan speed detected by hall IC when the
fan motor runs.
Malfunction
Decision
Conditions
P
When the fan runs with speed less than a specified one for 15 seconds or more when the fan motor
running conditions are met
P
When connector detecting fan speed is disconnected
P
When malfunction is generated 4 times, the system shuts down.
Supposed Causes
P
Malfunction of fan motor
P
The harness connector between fan motor and PC board is left in disconnected, or faulty connector
P
Fan does not run due to foreign matters tangled
P
Clearing condition: Operate for 5 minutes (normal)
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector, or parts damage may be
occurred.
Replace the outdoor unit fan motor.
Connect the connector.
Remove the foreign matter.
YES
NO
Are fan motor
connectors
disconnected?
Replace the outdoor unit fan motor.
NO
YES
Is the pulse input?
Check No. 11
Check for pulse input
for number of rotations
on the outdoor unit
PC board.
Replace the outdoor unit PC board.
YES
NO
NO
YES
Is there
any foreign matter
around the fan?
Can the fan be
easily rotated by hand?
(S2584)
RZQ - Final.book Page 62 Wednesday, September 8, 2004 8:40 AM
Summary of Contents for RZQ71~125B7V3B
Page 1: ...Service Manual ESIE04 01 RZQ71 125B7V3B Sky Air Inverter R 410A B series ...
Page 2: ......
Page 24: ...ESIE04 01 1 2 Part 1 System Outline 3 1 1 5 ...
Page 32: ...General Outline Outdoor Units ESIE04 01 1 10 Part 1 System Outline 3 1 1 4 5 ...
Page 64: ...General Outline Indoor Units ESIE04 01 1 42 Part 1 System Outline 3 1 1 4 5 ...
Page 76: ...Specifications ESIE04 01 1 54 Part 1 System Outline 3 1 1 4 5 ...
Page 92: ...Functional Diagrams ESIE04 01 1 70 Part 1 System Outline 3 1 1 4 5 ...
Page 94: ...ESIE04 01 1 72 Part 1 System Outline ...
Page 122: ...Wiring Diagrams ESIE04 01 1 100 Part 1 System Outline 3 1 1 4 5 ...
Page 140: ...ESIE04 01 2 2 Part 2 Functional Description 3 1 2 5 ...
Page 162: ...General Functionality ESIE04 01 2 24 Part 2 Functional Description 3 1 2 4 5 ...
Page 200: ...Outdoor Unit Functional Concept ESIE04 01 2 62 Part 2 Functional Description 3 1 2 4 5 ...
Page 202: ...ESIE04 01 3 2 Part 3 Troubleshooting 3 1 3 5 ...
Page 288: ...Error Codes Outdoor Units ESIE04 01 3 88 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 312: ...Additional Checks for Troubleshooting ESIE04 01 3 112 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 314: ...ESIE04 01 4 2 Part 4 Commissioning and Test Run 3 1 4 5 ...
Page 356: ...ESIE04 01 5 2 Part 5 Disassembly and Maintenance 3 1 5 ...
Page 484: ...ESIE04 01 viii Index 3 1 4 5 ...