ESIE04-01
Outdoor Unit Functional Concept
Part 2 – Functional Description
2–45
3
2
4
5
1
3.3.3
Low Pressure Protection Control
Outline
In order to prevent abnormal low pressures in the system, the below control function will be activated.
Low pressure is measured by the low pressure sensor.
Flow chart
Parameters
Normal operation
Lp < 0.49
MPa
Normal operation
&
(When cooling operation)
(When heating operation)
• Within 5 minutes after defrosting
• Lp < 0.1 MPa coninuously
Upper limit A Hz
Copmressor upper
limit frequency
B Hz
Compressor upper
limit frequency
C Hz
Compressor upper limit
frequency
C Hz
Compressor stop: O Hz
Malfunction stop (E4 indication)
• Within 5 minutes after
starting
• Within 10 minutes after
defrosting
&
• OR
• Lp < 0.15 Mpa
&
• Lp > 0.59 Mpa
• 30 sec elapsed
10 times or less
stopping in 200 minutes
LP < 0.1 MPa continues
for 5 minutes
10 times or less stopping
in 200 minutes
Lp < 0.1 MPa
LP > 0.15 MPa
Condition D*
Condition D*
LP > 0.25 MPa
LP > 0.2 MPa
Stopped 11 times in 200 minutes
• Within 5 minutes after starting
• After 10 minutes after defrosting
Condition D* : &
• OR
• Lp > 0.15 Mpa
RZQ71B
RZQ100 ~125B
A Hz
109 Hz
123 Hz
B Hz
62 Hz
62 Hz
C HZ
48 Hz
62 Hz
RZQ - Final.book Page 45 Wednesday, September 8, 2004 8:40 AM
Summary of Contents for RZQ71~125B7V3B
Page 1: ...Service Manual ESIE04 01 RZQ71 125B7V3B Sky Air Inverter R 410A B series ...
Page 2: ......
Page 24: ...ESIE04 01 1 2 Part 1 System Outline 3 1 1 5 ...
Page 32: ...General Outline Outdoor Units ESIE04 01 1 10 Part 1 System Outline 3 1 1 4 5 ...
Page 64: ...General Outline Indoor Units ESIE04 01 1 42 Part 1 System Outline 3 1 1 4 5 ...
Page 76: ...Specifications ESIE04 01 1 54 Part 1 System Outline 3 1 1 4 5 ...
Page 92: ...Functional Diagrams ESIE04 01 1 70 Part 1 System Outline 3 1 1 4 5 ...
Page 94: ...ESIE04 01 1 72 Part 1 System Outline ...
Page 122: ...Wiring Diagrams ESIE04 01 1 100 Part 1 System Outline 3 1 1 4 5 ...
Page 140: ...ESIE04 01 2 2 Part 2 Functional Description 3 1 2 5 ...
Page 162: ...General Functionality ESIE04 01 2 24 Part 2 Functional Description 3 1 2 4 5 ...
Page 200: ...Outdoor Unit Functional Concept ESIE04 01 2 62 Part 2 Functional Description 3 1 2 4 5 ...
Page 202: ...ESIE04 01 3 2 Part 3 Troubleshooting 3 1 3 5 ...
Page 288: ...Error Codes Outdoor Units ESIE04 01 3 88 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 312: ...Additional Checks for Troubleshooting ESIE04 01 3 112 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 314: ...ESIE04 01 4 2 Part 4 Commissioning and Test Run 3 1 4 5 ...
Page 356: ...ESIE04 01 5 2 Part 5 Disassembly and Maintenance 3 1 5 ...
Page 484: ...ESIE04 01 viii Index 3 1 4 5 ...